GB100W NATURAL OR PROPANE BOILER

INSTALLATION AND OPERATING INSTRUCTIONS

Page 9

The boiler should be placed in the location selected for it. Refer to the BOILER LOCATION section in this manual. Ensure that the boiler is level from front to back and from side to side. Use metal shims to level the boiler. NEVER use wood, plastic or other combustible materials as shims.

All heating system piping must be installed in accordance with the ANSI/ASME Boiler and Pressure Vessel Code, Section IV, and ANSI/ ASME CSD-1, Standard for Controls and Safety Devices for Automatically Fired Boilers. All applicable local codes and ordinances must also be followed.

If the boiler is installed above any radiation elements it must be fitted with a low water cutoff device, L.W.C.O., installed above the normal boiler water level.

Circulators

A TACO 007 circulator has been supplied as standard equipment with the boiler. The 007 is sized for use in a closed heating system with a 30 psi, 207 kPa, maximum operating pressure. If the 007 circulator furnished with this boiler does not have the required capacity for the system in which it is to be installed, an extra zone circulator must be provided. A circulator with a higher capacity may also be used. Figure 5 depicts the performance curve for the TACO 007 circulator.

Piping For Use With Cooling Units

The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler. Appropriate valves must be used to prevent the chilled water from entering the boiler. See Figure 6 for the proper piping layout.

When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device, the piping system must be equipped with flow- control valves or some other automatic means of preventing gravity circulation of the boiler water during the cooling cycle.

Figure 5: TACO 007 Performance Curve

 

10

 

 

 

 

 

 

 

WATEROFFEET-

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAD

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TACO 007 CIRCULATOR

 

 

 

 

 

 

PERFORMANCE CURVE

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5

10

 

15

20

FLOW - GPM

25

Image 9
Contents GB100W Before YOU Start ContentsBoiler Location Boiler Ratings and CapacitiesFront Clearances to Combustible ConstructionVent and Chimney Dimensions Combustible Floor OptionCombustion AIR Combustion Air Duct Sizing Vent ConnectionsChimney Inspection & Sizing Common Vent SystemsVent Dampers Heating System Piping Heating System PipingPiping For Use With Cooling Units CirculatorsPumped Blend System BypassGAS Supply Piping Equivalent Length ChartReverse Acting Aquastats Gas Pipe CapacityElectrical Power Connections Electrical WiringThermostat Installation Vent DamperFenwal/Honeywell Direct Ignition Theoriginalwire Bereplacedwith Ifanyof ItmustBereplaced Equivalent Withthisappliancemust ThermoplasticwireoritsHoneywell Continuous Pilot Ignition Multi Zone Diagram Flame Roll-out Safety Shutoff System Boiler SET UPFor Your Safety Read Before Operating Lighting InstructionsWhat to do if YOU Smell GAS Instructions Dallumage Pour Votre Sécurité Lisez Avant DallumerComment Couper Ladmission DE GAZ DE Lappareil QUE Paire SI Vous Sentez UNE Odeur DE GAZTo Turn OFF GAS to Appliance Operating InstructionsQUE Faire SI Vous Sentez UNE Odeur DE GAZ Pour Votre Sécurité Lisez Avant DE Mettre EN MarcheBoiler Operation Continuous Pilot SystemIntermittent & Direct Ignition Systems Pilot Adjustment Boiler Checking & AdjustmentGas Pressure Adjustment Input RateBoiler Maintenance Instructions to the Installer Vent SystemControls GB100 Series Repair Parts Replacement PartsSpark Ignition Honeywell Canadian Supplement Limited Lifetime Warranty For Residential Water Boilers Shortness of breath Page North ELM Street WESTFIELD, MA 01085 TEL 562-9631 FAX 413