Net Safety Monitoring Inc.
RELAY OPTIONS
Use to set the alarm level, coil status and latch status for the Low and High relays (Fault Alarm is fixed).
The following table describes the default settings for the sensor.
Table 4: Default Relay Settings
|
| Alarm Levels |
| Relay Coil | ||||
|
|
|
| Status |
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
Millennium |
|
|
| Latching |
| LatchingNon | Energized | |
|
|
|
|
|
|
|
| |
Model Number | Low | High | Fault |
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| Energized |
|
|
|
|
| |
ST1400 | 20% | 22% |
|
| * |
| * | |
|
|
| ||||||
(25%range) |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Setting Relay Options
There are two settings for Relay Options: Low and High. The Fault Relay is fixed as
Step 1: | When Set Relay Options YES? displays press the Calibration |
| Button or use the Reed Switch to select. |
| The flashing YES confirms the selection. |
Step 2: | The message Set Low displays. Low alarm |
| in increments of 1, beginning at 10 and cannot be set above 20. |
Step 3: | When the required level displays, press the Calibration Button or |
| use the Reed Switch to select. |
| The level chosen will flash to confirm the selection. |
Step 4: | The message Coil Status displays. The display then shows |
| Energized YES? and then |
Step 5: | Press the Calibration Button or use the Reed Switch to select. |
| The flashing YES confirms the selection. If no selection is made, the |
| Coil Status option is repeated. |
Step 6: | The message Latch Status displays. The display then shows |
| Latching YES? and then |
Step 7: | Press the Calibration Button or use the Reed Switch to select. |
| The flashing YES confirms the selection. If no selection is made, the |
| Latch Status option is repeated. |
Step 8: | The message Set High displays. |
| The High Alarm level must be set between 21 and 25. The High |
| Alarm level is displayed in increments of 1 beginning at the Low |
| Alarm |
Step 9: | Repeat Steps 4 through 7 to complete the High Alarm level, coil |
| and latch status settings. |
Note: If no selection is made, a 5 minute timer expires, in which case the unit returns to normal operation.