Appendix B: RESISTANCE TABLE IN OHMS

Distance (Feet)

AWG #20

AWG #18

AWG #16

AWG #14

AWG #12

AWG #10

AWG #8

100

1.02

0.64

0.40

0.25

0.16

0.10

0.06

200

2.03

1.28

0.80

0.51

0.32

0.20

0.13

300

3.05

1.92

1.20

0.76

0.48

0.30

0.19

400

4.06

2.55

1.61

1.01

0.64

0.40

0.25

500

5.08

3.20

2.01

1.26

0.79

0.50

0.31

600

6.09

3.83

2.41

1.52

0.95

0.60

0.38

700

7.11

4.47

2.81

1.77

1.11

0.70

0.44

800

8.12

5.11

3.21

2.02

1.27

0.80

0.50

900

9.14

5.75

3.61

2.27

1.43

0.90

0.57

1000

10.20

6.39

4.02

2.53

1.59

1.09

0.63

1250

12.70

7.99

5.03

3.16

1.99

1.25

0.79

1500

15.20

9.58

6.02

3.79

2.38

1.50

0.94

1750

17.80

11.20

7.03

4.42

2.78

1.75

1.10

2000

20.30

12.80

8.03

5.05

3.18

2.00

1.26

2250

22.80

14.40

9.03

5.68

3.57

2.25

1.41

2500

25.40

16.00

10.00

6.31

3.97

2.50

1.57

3000

30.50

19.20

12.00

7.58

4.76

3.00

1.88

3500

35.50

22.40

14.10

8.84

5.56

3.50

2.21

4000

40.60

25.50

16.10

10.00

6.35

4.00

2.51

4500

45.70

28.70

18.10

11.40

7.15

4.50

2.82

5000

50.10

32.00

20.10

12.60

7.94

5.00

3.14

5500

55.80

35.10

22.10

13.91

8.73

5.50

3.46

6000

61.00

38.30

24.10

15.20

9.53

6.00

3.77

6500

66.00

41.50

26.10

16.40

10.30

6.50

4.08

7000

71.10

44.70

28.10

17.70

11.10

7.00

4.40

7500

76.10

47.90

30.10

19.00

12.00

7.49

4.71

8000

81.20

51.10

23.10

20.20

12.70

7.99

5.03

9000

91.40

57.50

36.10

22.70

14.30

8.99

5.65

10 000

102.00

63.90

40.20

25.30

15.90

9.99

6.28

Note: Resistance shown is one way. This figure should be doubled when determining closed loop resistance.

MLP-A/AR/AD-ST1400-25

21

Image 26
Contents Millennium Page Important Information WarrantyContact Information Table of Contents How to Return Equipment MaintainManual SensorController ProductOption PlanLocate CONTROLLER/SENSOR External Equipment InstallUnpack Field Installation WireConnecting Wires MountElectromechancial Relay Board Board AssemblySolid State Relay Board Modbus TerminalsRS-485 Communication Sensor Board Terminals Controller WireTerminal Board Power Controller Sensor and ControllerWiring-Sensor Separation Sensor SeparationCurrent Output NON-ISOLATED/ISOLATED WiringTerminal Connection Remote Reset Modbus TerminationOperate Scrolling 8-character displayStatus LED State Current O/P RTU RegistersCalibration Button Accessing the Main Menu Magnetic Reed SwitchPower Up Current Loop Measurement Test JacksDisplay Calibration ProcedureCalibrate ShowsCalibration Failure Review Relay SettingsMonitor Model Number Low High Fault Setting Relay OptionsAlarm Levels Relay Coil Status Millennium Relay OptionsBaud Rate Set Low Power Options OptionalNode Address Modbus OptionsRemote Reset Sensor FaultManual Reset Non-standard O2 LevelsModbus MaintainRelays Optional CurrentT1Y 7J7 Spare PARTS/ACCESSORIESDescription Net Safety Part Number Face Rotation OptionRotate PCB Assembly Appendix aAppendix B Resistance Table in Ohms Sensor Specifications Sensor Element