Figure 5: Wiring—Controller and Sensor
Terminal Board
RST |
+24V |
COM |
RST |
| |
+24V |
| |
Power | ||
COM | ||
Terminals | ||
| ||
ISO |
| |
|
|
SENSOR AND CONTROLLER
WARNING:
Power to the unit must be OFF before wiring.
Note: The Sensor may be factory installed to the Controller. If so, you need only connect the Power Terminals.
1.Remove the Controller’s Housing Cover.
2.Connect the Sensor to the Sensor Terminals (if necessary) and the Output Terminals to the output signal wires.
Table 1: Controller/Sensor Connections
|
| |
A |
| ISO |
|
| |
B | Modbus RTU | Red+ |
|
| |
COM | Terminals | Blk |
| ||
- | to PLC |
|
|
| |
|
| Shld |
Red
Blk
-Sensor
- Terminals
Shld
Sensor Board Terminals
Sensor |
| Controller |
Wire |
| (Sensor Board) |
|
|
|
Red | = | Red (+24 V) |
Black | = | Blk (Sig) |
|
| - |
|
| - |
|
|
|
Shield | = | Shld |
|
|
|
Terminal Board Power
Controller |
| Power |
(Terminal Board) |
| Connections |
|
|
|
RST | = | Remote Reset |
+24V | = | Power (+) |
COM | = | Power |
= | Current Loop | |
|
| Output |
ISO | = | +24 V isolated |
|
| |
|
|
|
Sensor Board
Sensor Wires
Note: For Sensor Separation instructions, see Figure 6,
3.Replace the Controller’s Housing Cover.
4.Turn Controller On.
5.Ensure display reads Start Delay , Status LED is Red Slow Flash and current output displays 3.0 mA. This is the
RS-485 Communication
Connect devices in a chain via the Modbus terminals. The last device in the chain requires end of line termination (refer to "MODBUS Termination" on page 9).