Millennium Enterprises AD-ST1400-25 RS-485 Communication, Sensor and Controller, Connections

Page 11

Net Safety Monitoring Inc

Figure 5: Wiring—Controller and Sensor

Terminal Board

RST

+24V

COM

RST

 

+24V

 

Power

COM

4-20

Terminals

 

ISO

 

 

 

SENSOR AND CONTROLLER

WARNING:

Power to the unit must be OFF before wiring.

Note: The Sensor may be factory installed to the Controller. If so, you need only connect the Power Terminals.

1.Remove the Controller’s Housing Cover.

2.Connect the Sensor to the Sensor Terminals (if necessary) and the Output Terminals to the output signal wires.

Table 1: Controller/Sensor Connections

 

 

4-20

A

 

ISO

 

 

B

Modbus RTU

Red+

 

 

COM

Terminals

Blk

 

-

to PLC

 

 

 

 

 

Shld

Red

Blk

-Sensor

- Terminals

Shld

Sensor Board Terminals

Sensor

 

Controller

Wire

 

(Sensor Board)

 

 

 

Red

=

Red (+24 V)

Black

=

Blk (Sig)

 

 

-

 

 

-

 

 

 

Shield

=

Shld

 

 

 

Terminal Board Power

Controller

 

Power

(Terminal Board)

 

Connections

 

 

 

RST

=

Remote Reset

+24V

=

Power (+)

COM

=

Power (-)

4-20

=

Current Loop

 

 

Output

ISO

=

+24 V isolated

 

 

4-20 power

 

 

 

Sensor Board

Sensor Wires

Note: For Sensor Separation instructions, see Figure 6, "Wiring—Sensor Separation", on page 7.

3.Replace the Controller’s Housing Cover.

4.Turn Controller On.

5.Ensure display reads Start Delay , Status LED is Red Slow Flash and current output displays 3.0 mA. This is the start-up delay sequence which will last approximately 90 seconds.

RS-485 Communication

Connect devices in a chain via the Modbus terminals. The last device in the chain requires end of line termination (refer to "MODBUS Termination" on page 9).

Note: If the 4-20 mA signal is not used, connect a jumper between the 4-20 terminal and the COM terminal on the Terminal Board.

MLP-A/AR/AD-ST1400-25

6

Image 11
Contents Millennium Page Important Information WarrantyContact Information Table of Contents Maintain How to Return EquipmentProduct SensorController ManualOption PlanLocate CONTROLLER/SENSOR External Equipment InstallUnpack Mount WireConnecting Wires Field InstallationModbus Terminals Board AssemblySolid State Relay Board Electromechancial Relay BoardSensor and Controller Sensor Board Terminals Controller WireTerminal Board Power Controller RS-485 CommunicationSensor Separation Wiring-Sensor SeparationCurrent Output NON-ISOLATED/ISOLATED WiringTerminal Connection Modbus Termination Remote ResetScrolling 8-character display OperateStatus LED State Current O/P RTU RegistersCalibration Button Current Loop Measurement Test Jacks Magnetic Reed SwitchPower Up Accessing the Main MenuShows Calibration ProcedureCalibrate DisplayCalibration Failure Review Relay SettingsMonitor Relay Options Setting Relay OptionsAlarm Levels Relay Coil Status Millennium Model Number Low High FaultModbus Options Set Low Power Options OptionalNode Address Baud RateNon-standard O2 Levels Sensor FaultManual Reset Remote ResetCurrent MaintainRelays Optional ModbusFace Rotation Option Spare PARTS/ACCESSORIESDescription Net Safety Part Number T1Y 7J7Appendix a Rotate PCB AssemblyAppendix B Resistance Table in Ohms Sensor Specifications Sensor Element