Millennium Enterprises AD-ST1400-25, MLP-A/AR Maintain, Relays Optional, Modbus, Current

Page 23

Net Safety Monitoring Inc

OUTPUTS

Relays - Optional

Note: The fault relay output is not used to activate an automatic shutdown procedure. The fault output indicates a potential problem with the Controller not an alarm condition.

Standard electro-mechanical relay outputs have Form C SPDT contacts rated 5 Amperes at 30 V dc/ 250 V ac. Three relay outputs are available; one for Fault; one for Low alarm; and one for High alarm. All relays have normally open and normally closed contacts available at the output terminals.

The fault relay is set for normally energized operation and is non-latching. If a system fault is detected, the fault relay becomes de-energized. The fault relay is factory set and cannot be altered. The Low alarm and High alarm relays can be selected for either normally energized or normally de-energized operation and latching/non-latching.

Modbus

Digital RS-485 Modbus RTU protocol is used.

Register 40001 = % output (read only)

Register 40002 = Status (read only)

Register 40101 = Reset latched alarms (write)

Note: Many registers are used by the controller. Please do not write outside the three registers.

Current

A 4-20 mA dc current output is used to transmit the alarm status and fault codes to other devices. This output can be wired for isolated or non-isolated operation. A 17.4 mA output indicates normal operation; a value >17.4 or <17.4 mA out- put indicates an abnormal amount of oxygen. Current output of 2.5 mA indi- cates the presence of a system fault.

STEP 7 — MAINTAIN

PERIODIC RESPONSE CHECK

We recommend a typical response check or calibration is performed on the Millennium every 3 months. A typical response check involves the application of calibration gas to the sensor, then the observation of the response LEDs, analog output, display and external monitoring equipment. Be sure to prevent unwanted response of external monitoring devices and equipment during this procedure. If the Millennium response to calibration gas is within its specified accuracy then it is not necessary to perform a calibration. For example, when 12% oxygen is applied, the response is expected to be between 10.4 mA (10% O2) and 12.96 mA (14% O2). An additional consideration is the accuracy tolerance of the calibration gas which may be + or - a few percent.

TROUBLESHOOT

Response to the input should be checked and, if necessary, calibration should be performed whenever any of the following occur. Refer to "Calibration Procedure" on page 13 for calibration instructions.

Excess negative drift is indicated by 2.5 mA current output

Sensor or transmitter is connected or disconnected

Long term exposure or high concentration exposure to gas

The Millennium is not designed to be repaired in the field. If a problem should develop, first calibrate the device and carefully check for faulty wiring. If it is determined that the problem is caused by an electronic failure, the device must be returned to the factory for repair. Refer "How to Return Equipment" on page 19 for detailed instructions.

MLP-A/AR/AD-ST1400-25

18

Image 23
Contents Millennium Page Important Information WarrantyContact Information Table of Contents Maintain How to Return EquipmentProduct SensorController ManualOption PlanLocate CONTROLLER/SENSOR External Equipment InstallUnpack Mount WireConnecting Wires Field InstallationModbus Terminals Board AssemblySolid State Relay Board Electromechancial Relay BoardSensor and Controller Sensor Board Terminals Controller WireTerminal Board Power Controller RS-485 CommunicationSensor Separation Wiring-Sensor SeparationCurrent Output NON-ISOLATED/ISOLATED WiringTerminal Connection Modbus Termination Remote ResetScrolling 8-character display OperateStatus LED State Current O/P RTU RegistersCalibration Button Current Loop Measurement Test Jacks Magnetic Reed SwitchPower Up Accessing the Main MenuShows Calibration ProcedureCalibrate DisplayCalibration Failure Review Relay SettingsMonitor Relay Options Setting Relay OptionsAlarm Levels Relay Coil Status Millennium Model Number Low High FaultModbus Options Set Low Power Options OptionalNode Address Baud RateNon-standard O2 Levels Sensor FaultManual Reset Remote ResetCurrent MaintainRelays Optional ModbusFace Rotation Option Spare PARTS/ACCESSORIESDescription Net Safety Part Number T1Y 7J7Appendix a Rotate PCB AssemblyAppendix B Resistance Table in Ohms Sensor Specifications Sensor Element