SENSOR SEPARATION

Figure 6: WiringSensor Separation

Power

Terminals*

Modbus RTU

Terminals

to PLC*

Sensor

Terminals*

Terminal Board

To designated terminal board

and oxygen sensor. See MAN-0081

RST

Multi-purpose Junction Box manual

+24V

COM

4-20

ISO

Red

Blk

Shld

Sensor Board

As the Sensor must be located in one location and the Controller in a location where it can be easily reached, it is often necessary to “separate” the Controller and Sensor.

The Sensor separation kit (SEP) is composed of a junction box and terminal strip. Refer to the Net Safety Multi-purpose Junction Box manual (MAN-0081) for terminal designation when wiring for sensor separation.

Shielded copper instrument wire (minimum 18 AWG) should be used for separations up to 500 feet. Shielded copper instrument wire (minimum

16 AWG) should be used for separations up to 2000 feet. Consult the factory if a greater separation distance is required.

Ensure that the appropriate wire is used for Class 1/Division 1 hazardous applications.

Note: If the 4-20 mA signal is not used, connect a jumper between the 4-20 terminal and the COM terminal on the Terminal Board.

MLP-A/AR/AD-ST1400-25

7

Image 12
Contents Millennium Page Warranty Contact InformationImportant Information Table of Contents How to Return Equipment MaintainSensor ControllerManual ProductPlan Locate CONTROLLER/SENSOROption Install UnpackExternal Equipment Wire Connecting WiresField Installation MountBoard Assembly Solid State Relay BoardElectromechancial Relay Board Modbus TerminalsSensor Board Terminals Controller Wire Terminal Board Power ControllerRS-485 Communication Sensor and ControllerWiring-Sensor Separation Sensor SeparationNON-ISOLATED/ISOLATED Wiring Terminal ConnectionCurrent Output Remote Reset Modbus TerminationOperate Scrolling 8-character displayRTU Registers Calibration ButtonStatus LED State Current O/P Magnetic Reed Switch Power UpAccessing the Main Menu Current Loop Measurement Test JacksCalibration Procedure CalibrateDisplay ShowsReview Relay Settings MonitorCalibration Failure Setting Relay Options Alarm Levels Relay Coil Status MillenniumModel Number Low High Fault Relay OptionsSet Low Power Options Optional Node AddressBaud Rate Modbus OptionsSensor Fault Manual ResetRemote Reset Non-standard O2 LevelsMaintain Relays OptionalModbus CurrentSpare PARTS/ACCESSORIES Description Net Safety Part NumberT1Y 7J7 Face Rotation OptionRotate PCB Assembly Appendix aAppendix B Resistance Table in Ohms Sensor Specifications Sensor Element