Aprilaire 1850w, 1830 Ducting for TWO Zone Installations, Whole-Home Primary Zone Installation

Page 12

DUCTING FOR TWO ZONE INSTALLATIONS

In this installation the dehumidifier controls the humidity in two separate zones, a Primary and Secondary Zone.. The dehumidifier will dehumidify the Primary Zone as the first priority, and will switch to the Secondary Zone after the dehumidification needs of the Primary Zone have been satisfied..

IMPORTANT: Normally Closed dampers must be installed in the ducts serving the Primary Zone and Normally Open dampers installed in the ducts serving the Secondary Zone.

Required Components

10” Ductwork and Fittings Grilles with 10” Duct Collars Drain Line

2 – Aprilaire Model 6510, 10” Normally Closed Damper

2 – Aprilaire Model 6610, 10” Normally Open Damper

24 VAC Transformer (40VA min..) for Dampers

NOTE: 5442 Basement Kit includes 2 – 6510 Dampers,

2 – 6610 Dampers and a 24VAC (40VA) transformer

FIGURE 18 – Whole-Home Primary Zone Installation

TO/FROM

SUPPLY DUCT

PRIMARY ZONE

 

RETURN DUCT

NORMALLY CLOSED

DAMPERS

SUPPLY TO

6 ftSECONDARY ZONE MIN

RETURN FROM

SECONDARY ZONE

NORMALLY OPEN DAMPER

NORMALLY OPEN DAMPER

 

 

 

90-1875

FIGURE 19 – Whole-Home Secondary Zone Installation

 

 

 

 

TO /FROM

SUPPLY DUCT

 

 

 

 

 

SECONDARY ZONE

 

 

RETURN

 

NORMALLY

 

DUCT

 

OPEN

 

 

 

DAMPER

 

NORMALLY

 

SUPPLY TO

RETURN FROM

OPEN

 

PRIMARY ZONE

PRIMARY ZONE

DAMPER

 

 

 

 

 

 

 

 

NORMALLY CLOSED DAMPER

NORMALLY CLOSED DAMPER

 

 

 

 

 

90-1895

12

 

 

 

Image 12
Contents Installation Instructions Safety InstructionsTable of Contents Specifications SET UP Dehumidifier for Installation Standard basement and attic installations fully ductedCloset installations Crawl space, Sealed Attics or basement installationsControl Location To move the controlDetach the on-board control by removing the four Hard Wiring Minimum Wire Size AWGVoltage Minimum Circuit CapacityHard Wiring Wiring InstructionsReattach the electrical service panel and side panel Location Considerations Drain Installation Condensate PAN, Condensate Pump and Float SwitchLeveling Ducting to Hvac System Basement and Attic Installations Required ComponentDuctwork Ducting NotesDucting to Hvac System Closet Installations Optional ComponentOptional Components Ductwork Grilles with 10 Duct CollarsDucting for TWO Zone Installations Whole-Home Primary Zone InstallationExternal Control Crawl SPACE/SEALED Attic ControlWiring the Dehumidifier to the Hvac System and Zone Dampers Wiring to the Hvac SystemOptional W & Y Wiring Wiring to Zone DampersSystem SET-UP & Checkout Zone 90-1854selectionsExternal Control DEH W/ACSystem SET-UP & Checkout Dehumidification OnlyZoning and/or Ventilation 90-1854energizedCrawl Space or Sealed Attic Remote Control Using Model Sampling will show on the displayTWO Zone Primary and Secondary Press the ON/OFF button to turn the dehumidifier control onIntake Hood AWG Wire Installation & WiringVentilation Installation VentilationOutdoor Temperature Sensor Installation VentilationVENT-AUTO & VENT-TIMED Dehumidifier can ventilate in four modesRecord the required CFM Determine Fresh AIR Delivery RateCFM Required CFM DeliveredFor 3 seconds to access Disabled screen appearsRepeatedly until the Vent Adjusting Ventilation Time After Initial SET UP Sequence of OperationDehumidifying the Fresh AIR Ventilation with AN External ControlTroubleshooting Diagnostic CodesDiagnostic Codes Troubleshooting Troubleshooting Guide Service Parts 10010759 B2206316A