TROUBLESHOOTING (continued)
TABLE 4 – Diagnostic Codes (continued)
Diagnostic
Code
Failure Mode
Action
Reset
E7 | Float Switch Open | 1. | Empty the condensate pan.. |
|
|
| |
|
| 2. | Check the float switch connection at the control board.. |
|
|
|
|
|
| 3. | If not using a float switch, verify jumper is between float switch terminals on dehumidifier |
| |||
|
|
| control board.. |
|
|
|
|
|
| 4. | If the problem persists, replace the float switch.. |
|
|
|
|
|
|
|
|
|
|
|
|
E8 | Inlet Air Temperature | 1. | Verify all ductwork is properly sealed.. |
|
|
| |
| Out of 50°F – 104°F | 2. | If no signs of leak points, contact Technical Support.. |
|
|
|
|
| or dew point below |
|
|
|
|
|
|
| 40°F |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E9 | Outdoor Temperature | 1. | Check the sensor connection at the power board.. |
|
|
| |
Outdoor | Resistance |
| |||||
| Sensor Open or | 2. Remove the wires from the terminals and measure | Temperature |
|
| ||
|
|
|
| ||||
| Shorted |
| the resistance.. A short circuit will have a resistance |
|
|
|
|
|
| 0°F | 84,500 Ohms |
|
| ||
|
|
| very close to 0 Ohms and an open circuit will have |
|
|
|
|
|
|
| 20°F | 46,000 Ohms |
|
| |
|
|
| a very very high resistance.. The table at right can |
|
| ||
|
|
|
|
|
|
| |
|
|
| 40°F | 26,000 Ohms |
|
| |
|
|
| be used to approximate the resistance based on |
|
| ||
|
|
|
|
|
|
| |
|
|
| outdoor temperature.. | 60°F | 15,500 Ohms |
|
|
|
| 3. | If the sensor is not reading correctly, replace the | 80°F | 9,500 Ohms |
|
|
|
|
| sensor, Part No.. 8052.. |
|
|
|
|
|
|
| 100°F | 6,000 Ohms |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|