VENTILATION (continued)
VENT-AUTO & VENT-TIMED
The dehumidifier can ventilate in four modes.
Vent-Timed: Ventilation occurs based only on time setting; no temperature restrictions..
Vent-Auto-B: Ventilation prevented when outdoor temperature is below 0°F and above 100°F.. Between 0°F – 20°F ventilation is only allowed during a HVAC heat call..
Vent-Auto-C: Ventilation prevented when outdoor temperature is below 0°F and above 100°F..
Vent-Auto-D: Ventilation prevented when outdoor temperature is below 0°F and above 90°F.. Between 0°F – 40°F ventilation is only allowed during a HVAC heat call..
Vent-Auto-B, -C, -D modes apply outdoor temperature limits and require an outdoor temperature sensor to be installed..
OUTDOOR TEMPERATURE SENSOR INSTALLATION
The Outdoor Temperature Sensor should be installed outside in a shaded location, or in the outdoor air intake duct..
Figure 27 – ODT Mounted Outside
| NORTH, EAST | OUTDOOR |
| OR WEST SIDE |
| OF HOME | TEMPERATURE |
| | SENSOR |
| | SENSOR |
| | SENSOR |
OUTDOOR | ABOVE EXPECTED | BRACKET |
|
TEMPERATURE SENSOR | |
SNOW LINE | |
LEADS | |
| |
| | B2202617-D |
Figure 28 – ODT Mounted in Intake Duct
CENTER LINE
36" MAX . 
OUTSIDE WALL
B2202617-E