Aprilaire 1830, 1850 System SET-UP & Checkout, Dehumidification Only, Zoning and/or Ventilation

Page 17

SYSTEM SET-UP & CHECKOUT (continued)

Installer Test Mode

If everything is properly wired, the dehumidifier and all of the wired components will turn on and off during Installer Test Mode to demonstrate that all are properly operating.. Installer Test Mode lasts for four (4) minutes.. If the ON/OFF button is pressed during test mode, the dehumidifier will exit Installer Test Mode and return to the OFF screen..

Dehumidification Only

If the dehumidifier is not already OFF, press the ON/OFF button to turn it off..

90-1854

Press and hold the ON/OFF button and MODE buttons for 3 seconds.. The measured humidity, AIR SAMPLING and TEST will show on the display.. If wired to the

90-1854HVAC system, the HVAC blower will turn on and if there is/are damper(s) wired to the DEH DAMPER terminals of the control, the damper(s) will energize..

After three (3) minutes the dehumidifier compressor will turn on and DEHUMIDIFYING will replace AIR SAMPLING on the control screen..

90-1854

After one minute of compressor operation, all outputs will turn off and DONE will blink for 3 seconds and then return to the OFF screen..

90-1854

90-1854

Zoning and/or Ventilation

If the dehumidifier has been set up for ventilation, VENTILATING will appear on the display throughout Installer Test Mode, and the ventilation damper will be

90-1854energized..

If the dehumidifier has been set up for zoning, PRIMARY ZONE will show on the display for the first minute of dehumidifier blower operation.. After one minute,

90-1854SECONDARY ZONE will show on the display and the zone dampers will de-energize..

17

Image 17
Contents Safety Instructions Installation InstructionsTable of Contents Specifications Standard basement and attic installations fully ducted SET UP Dehumidifier for InstallationCloset installations Crawl space, Sealed Attics or basement installationsDetach the on-board control by removing the four Control LocationTo move the control Minimum Wire Size AWG Hard WiringVoltage Minimum Circuit CapacityReattach the electrical service panel and side panel Hard WiringWiring Instructions Location Considerations Leveling Drain InstallationCondensate PAN, Condensate Pump and Float Switch Required Component Ducting to Hvac System Basement and Attic InstallationsDuctwork Ducting NotesOptional Component Ducting to Hvac System Closet InstallationsOptional Components Ductwork Grilles with 10 Duct CollarsWhole-Home Primary Zone Installation Ducting for TWO Zone InstallationsCrawl SPACE/SEALED Attic Control External ControlWiring to the Hvac System Wiring the Dehumidifier to the Hvac System and Zone DampersOptional W & Y Wiring Wiring to Zone DampersSystem SET-UP & Checkout 90-1854selections ZoneExternal Control DEH W/ACDehumidification Only System SET-UP & CheckoutZoning and/or Ventilation 90-1854energizedSampling will show on the display Crawl Space or Sealed Attic Remote Control Using ModelTWO Zone Primary and Secondary Press the ON/OFF button to turn the dehumidifier control onInstallation & Wiring Intake Hood AWG WireVentilation Installation VentilationVentilation Outdoor Temperature Sensor InstallationVENT-AUTO & VENT-TIMED Dehumidifier can ventilate in four modesDetermine Fresh AIR Delivery Rate Record the required CFMCFM Required CFM DeliveredRepeatedly until the Vent For 3 seconds to accessDisabled screen appears Sequence of Operation Adjusting Ventilation Time After Initial SET UPDehumidifying the Fresh AIR Ventilation with AN External ControlDiagnostic Codes TroubleshootingDiagnostic Codes Troubleshooting Troubleshooting Guide Service Parts 10010759 B2206316A