TROUBLESHOOTING (continued)
TABLE 5 – Troubleshooting Guide
Symptom
Possible Reason
Troubleshooting Procedure
Dehumidifier does not | No power to unit.. | • Check that the dehumidifier is plugged in. |
|
|
|
turn on/run.. |
| • Check that the power switch is turned ON. |
|
|
|
|
| • Check that the control is turned ON. |
|
|
|
|
| • Check that the circuit breaker has not tripped. |
|
|
|
|
|
|
|
|
|
Dehumidifier blower is | Pressure drop across | • Check dehumidifier air filter and wash or replace. |
|
|
|
running but with little or | dehumidifier is higher | • Check for blocked duct work and clear. |
|
|
|
no airflow.. | than 0.4”w.c. for Model | • Verify that the outlet collar with backflow damper is installed on the outlet side of the dehumidifier. | |||
| 1830 or 0.6”w.c. for | ||||
| • Check if backflow damper is blocked or stuck and remove obstruction. |
|
| ||
| Model 1850/1850W.. |
|
| ||
|
|
|
|
| |
|
|
|
|
|
|
Dehumidifier blower is | Float switch open.. | • If float switch installed, check connections at control board and empty condensate pan. | |||
running but compressor |
| • If no float switch installed check that the jumper is installed at the float switch terminals on the | |||
is not.. |
| control board.. |
|
|
|
|
|
|
|
|
|
| Coil frosting.. | • Lack of or reduced airflow. Check dehumidifier air filter and wash or replace. |
|
| |
|
| • Check for blocked duct work. |
|
|
|
|
| • Inlet air conditions below 60°F. Increase the humidity setting. |
|
| |
|
|
|
|
|
|
| Inlet air temperature is | • Verify all ductwork is properly sealed. |
|
|
|
| outside of the 50°F – |
|
|
|
|
| 104°F range or the dew |
|
|
|
|
| point is below 40°F and |
|
|
|
|
| there is a demand for |
|
|
|
|
| dehumidification.. |
|
|
|
|
|
|
|
|
|
|
When zoned, the | Incorrect damper wiring | • Verify wiring between dampers and 24 VAC transformer. |
|
|
|
dehumidifier damper | or bad connection.. | • If wired for Two Zone operation, verify that 24 VAC transformer is 40 VA minimum. | |||
does not open in |
| • Check all wiring connections between dampers and control board. |
|
| |
INSTALLER TEST mode.. |
|
|
| ||
| • Verify the normally closed dampers are in the Primary Zone ductwork and the normally open | ||||
|
| ||||
|
| dampers are in the Secondary Zone ductwork.. |
|
|
|
|
|
|
|
|
|
The ventilation damper | Cycle time has been | • The damper will not open if the Ventilation Time has already been met. |
|
| |
does not open when the | met.. |
|
|
|
|
HVAC fan is active.. |
|
|
|
|
|
ODT error or outdoor air | • Check that the ODT is wired correctly to the |
|
|
| |
| Outdoor | Resistance |
| ||
| outside of ODT range.. | dehumidifier control board and connections are secure.. | Temperature |
| |
|
|
| |||
|
| • Check that the ODT is installed in the outdoor air | 0°F | 84,500 Ohms |
|
|
| intake according to the |
|
|
|
|
| 20°F | 46,000 Ohms |
| |
|
| Ventilation Section beginning on page 19.. |
| ||
|
|
|
|
| |
|
| 40°F | 26,000 Ohms |
| |
|
| • Remove the ODT leads from the dehumidifier control |
| ||
|
|
|
|
| |
|
| 60°F | 15,500 Ohms |
| |
|
| board and check the resistance.. Compare the reading |
| ||
|
| with the table shown.. | 80°F | 9,500 Ohms |
|
|
|
| 100°F | 6,000 Ohms |
|
|
|
|
|
|
|
|
|
|
|
|
|
Dehumidifier is not | Drain line blocked or unit | • Verify that the unit is level. |
|
|
|
draining properly.. | not level.. | • Check the drain line blockages and for a continuous downward slope. |
|
| |
|
|
|
|
|
|
The HVAC fan turns on | Dehumidifier is sampling | • The dehumidifier will turn on the HVAC fan during air sampling or as needed to meet the ventilation | |||
unexpectedly.. | or ventilation in | time.. |
|
|
|
| progress.. |
|
|
|
|
|
|
|
|
|
|
Dehumidifier is | Normal function.. | • Air is reheated across the condenser coil, resulting in a temperature rise between inlet and outlet. | |||
producing hot air.. |
|
|
|
|
|
|
|
|
|
|
|
26