Beckett CF1400 manual Operating the Burner, Set High-fire Air, Set Low-fire Air

Page 19

Section: Start the Burner

Operating the Burner

1.Move the low-fire hold switch to the low fire hold position (to hold burner in low fire when started).

2.Verify that the air adjusting cam (Figure 17, item d) has been set to the initial low-fire air setting as described under the ‘Initial Air Settings’ section.

3.Open the oil shutoff valves in the oil supply line to the burner.

4.Set the thermostat (or operating control) to call for heat.

5.Close the line switch to the burner. The burner motor should start immediately.

6.If the burner motor does not start, reset the motor overload switch (if so equipped) and press the reset switch of the burner primary control.

7.Vent the fuel unit as soon as the burner motor starts rotating. (For GeniSys 7505 control refer to the control manual for Priming the Pump procedure.)

To vent:

Attach a clear plastic tube to the air bleed valve (Figure 9 or 10 as applies, item p).

Place the end of the tube in a container to catch the oil. Then loosen the fuel unit air vent valve.

Tighten the air vent valve after all air has been purged.

IF burner stops during venting

-The burner primary control will lockout if

flame is not established within its time limit. This is typically 15 seconds for R7184B primary controls, but may be less for other flame supervisory controls.

-The burner may lockout several times during the period needed to purge all the air. To extend air venting time, press the red reset button for 1/2 second during the prepurge cycle to continue purging.

IF burner stops after flame is established

-Additional venting is probably required. Repeat the air venting procedure.

8.Once flame is steady, proceed to ‘Set High-fire Air’.

Set High-fire Air

1.Allow the burner to run at low fire until the appliance has warmed sufficiently.

2.Visually check the flame. The flame should not be dark orange or smoky. If the flame appears to be smoking, increase the amount of air by readjusting the damper indicator to a higher number.

3.Once the appliance has warmed, the high-firesetting can be checked and adjusted.

4.Locate the approximate air adjusting plate setting for high fire in Table 4a or 4b.

5.Place the low-fire hold switch in the high-fire position. The damper motor will begin to rotate after four seconds.

6.Use combustion test instruments to adjust the burner.

a.Adjust the air by moving the red cam to a lower number until a trace of smoke is achieved with CO2 level as high as possible (lowest possible O2).

Example: 13.5% CO2 (2.5% O2) with a trace of smoke.

b.Increase the air by increasing the red cam number to reduce CO2 by 2 percentage points at a zero smoke level. (Increase O2 by 3 percentage points at a zero smoke level.)

Example: Reduce CO2 from 13.5% to 11.5%, with zero smoke (or increase O2 from 2.5% to 5.5%).

c.A margin of reserve air has been added to accommodate variable conditions.

7.Check the breech draft pressure against the appliance manufacturer’s recommended setting (typically + 0.1” W.C.).

8.If the breech pressure is higher or lower than recommended level, adjust the appliance breech damper to achieve the specified setting. Recheck the smoke and CO2 levels. Adjust burner air if necessary.

9.Once all settings are complete and satisfactory, proceed to ‘Set Low-fire Air’.

Set Low-fire Air

1.Move the low-fire hold switch from the “High Fire position” to the “Low Fire Hold” position.

a.The damper will return to the low-fireair setting.

2.Check the smoke and CO2 (O2) levels.

a.Pull a smoke sample from the flue.

b.The sample should be clean (zero smoke level).

c.Check the CO2 (O2) level:

CO2 should be at 11 to 12% (O2 at 5.9 to 4.5%). If the CO2 is less than 11% (O2 more than 5.9%), decrease the air and check the smoke level.

3.Operate the burner from low fire to high fire and back to verify operation.

4.Turn the burner off. Wait one or two minutes (for chamber to clear) and then turn on again to verify starting characteristics.

5.Perform limit circuit performance test specified by appliance manufacturer to verify operation of burner/appliance combination.

CF1400/CF2300 Burner Manual

19

Image 19
Contents To the Homeowner or Equipment Owner Potential for Fire, Smoke and Asphyxiation HazardsContents Hazard Definitions General InformationFrozen Plumbing Water Damage Hazard Fuel Supply Oil Supply Pressure Control Required Pre-Installation ChecklistCombustion Air Supply ClearancesElectrical Supply Vent SystemVerify Burner Components Verify Firing RateAir Tube Capacity Versus Firebox Pressure Verify Air Tube± 1/8 Protect Against Stray Light Lockout Failure to follow these Mount the BurnerMount Air Tube to Burner Install NozzleCheck Electrode Settings Maintain Electrode Specifications Install Nozzle Line AssemblyDo not install valves in the return line Set Z DimensionFuel Unit By-pass Plug Factory-Installed Pump Bypass Plug Install Oil Supply To SpecificationsOil Supply/Return Lines One-pipe Oil System By-pass LoopBurner Fuel Flow Electrical shock can cause severe personal injury or death Wire the BurnerCan cause severe injury, death, or property damage Optional Components Typical Burner Sequence of OperationTypical Wiring 7505P Restricted Lockout Typical Burner Sequence of Operation 7184B ControlAsphyxiation, explosion or fire Tampering with, or bypassing safety controlsPrepare the Burner for Start-up Could lead to equipment malfunction and result CF2300 Initial Indicator Adjustment Plate Settings CF1400 Initial Indicator Adjustment Plate Settings Initial Head Position Set Appliance Limit Controls Initial Air SettingsPrepare the Fuel Unit for Air Venting Explosion and Fire Hazard Professional Service RequiredDisable Function Start the BurnerSet High-fire Air Operating the BurnerSet Low-fire Air Annual Service Maintenance and ServiceReplacement Parts Annual Professional Service RequiredBurner Replacement Parts Oil Valve Mounted on Junction Box 21789U Part Name Description CF1400 Part No CF2300 Part NoSK9930 SK9936 SK9932 Limited Warranty Information
Related manuals
Manual 24 pages 57.78 Kb