Beckett CF1400 manual Mount Air Tube to Burner, Install Nozzle Line Assembly, = 1-3/4 ± 1/16

Page 8

Section: Mount the Burner

Mount Air Tube to Burner

○ Slide the secondary adjusting plate (item f)

Remove the rear access door from the back of the

completely to the left on the indicator adjusting plate

(item e). Finger-tighten acorn nut (item c) to secure

burner for improved access to the interior.

the two plates together. Slide both plates completely

Attach the air tube to the burner with the bolts and acorn

to the left on the primary adjusting plate (item g) and

nuts provided. The acorn nuts must go on the outside of

finger-tighten acorn nut (item d).

the burner, with the bolts inserted from the inside.

○ Slide the completed adjusting plate assembly

 

 

over the nozzle line end. Move the plate assembly

Install Nozzle

and the nozzle line so the plate assembly fits into

See Figure 5. Install the oil nozzle in the nozzle adapter.

position as shown in Figure 6.

○ Install the spline nut (item b) on the end of the

Use a 3/4” open-end wrench to steady the nozzle

nozzle line, leaving the nut loosely placed so the

adapter and a 5/8” open-end wrench to turn the nozzle.

plates can be moved.

Tighten securely but do not overtighten.

○ Connect the high-voltage leads from the ignition

 

 

transformer to the electrodes.

Check Electrode Settings

Maintain Electrode

Specifications

Failure to properly maintain these specifications could cause ignition malfunction, puff-back of hot gases, heavy smoke, asphyxiation, explosion and fire hazards.

Check, and adjust if necessary, the critical dimensions P, Q, R and S shown in Figure 5. Verify that the oil tube assembly and electrodes are in good condition, with no cracks or damage.

Figure 5 – Nozzle and Nozzle Line Assembly

Legend (Figure 5)

PNozzle centerline to electrode tip - 1/4”

QNozzle to head - 1/4”

RNozzle face to electrode tip - 1/8”

SElectrode spacing - 3/32”

Install Nozzle Line Assembly

Insert the nozzle line assembly into the burner air tube as in Figure 6.

See Figures 6 and 7. Assemble the adjusting plate assembly per the instructions in the assembly packet.

Figure 6 – Nozzle Line Assembly in Burner

z (Measured from the flat front surface of the head to the end of the air tube, as shown).

a

Measure dimension Z from the flat surface between (not on) the raised fins.

Z = 1-3/4” ± 1/16”

Legend (Figures 6 & 7)

aAdjusting plate assembly

bSpline nut for securing nozzle line

cBottom acorn nut

dTop acorn nut (for setting dim. Z only)

eIndicator adjusting plate

fSecondary adjusting plate g Primary adjusting plate

8

Image 8
Contents Potential for Fire, Smoke and Asphyxiation Hazards To the Homeowner or Equipment OwnerContents Frozen Plumbing Water Damage Hazard General InformationHazard Definitions Pre-Installation Checklist Combustion Air SupplyClearances Fuel Supply Oil Supply Pressure Control Required Vent System Verify Burner Components Verify Firing Rate Electrical Supply± 1/8 Verify Air TubeAir Tube Capacity Versus Firebox Pressure Mount the Burner Protect Against Stray Light Lockout Failure to follow theseInstall Nozzle Check Electrode Settings Maintain Electrode SpecificationsInstall Nozzle Line Assembly Mount Air Tube to BurnerSet Z Dimension Fuel Unit By-pass Plug Factory-Installed Pump Bypass PlugInstall Oil Supply To Specifications Do not install valves in the return lineBurner Fuel Flow One-pipe Oil System By-pass LoopOil Supply/Return Lines Can cause severe injury, death, or property damage Wire the BurnerElectrical shock can cause severe personal injury or death Typical Burner Sequence of Operation Optional ComponentsTypical Wiring 7505P Typical Burner Sequence of Operation 7184B Control Restricted LockoutTampering with, or bypassing safety controls Prepare the Burner for Start-upCould lead to equipment malfunction and result Asphyxiation, explosion or fireInitial Head Position CF1400 Initial Indicator Adjustment Plate SettingsCF2300 Initial Indicator Adjustment Plate Settings Prepare the Fuel Unit for Air Venting Initial Air SettingsSet Appliance Limit Controls Professional Service Required Disable FunctionStart the Burner Explosion and Fire HazardSet Low-fire Air Operating the BurnerSet High-fire Air Maintenance and Service Replacement PartsAnnual Professional Service Required Annual ServiceBurner Replacement Parts Part Name Description CF1400 Part No CF2300 Part No Oil Valve Mounted on Junction Box 21789USK9930 SK9936 SK9932 Limited Warranty Information
Related manuals
Manual 24 pages 57.78 Kb