Section: Mount the Burner
Figure 7 – Adjusting Plate Assy. |
|
| ||
d | b | e f | c | g |
#9 Setting
Set “Z” Dimension
1.Replace the rear access door on the burner, making sure that the adjusting plate assembly is seated in the recessed area in the housing.
2.Loosen acorn nut (item c) and spline nut (item b). Move nozzle line forward to the maximum head setting #9 and tighten acorn nut (item c).
3.Loosen acorn nut (item d). Slide the nozzle line and plate assembly until dimension “Z” in Figure 6 is
4.Attach the oil line from the oil valve to the nozzle line end. Tighten securely.
5.Before proceeding, check dimension “Z” once again. Loosen acorn nut (item d) if necessary to reposition the nozzle line. Once dimension “Z” is set, do not loosen acorn nut (item d) again.
6.Loosen acorn nut (item c) to set the head at the proper setting for the application and tighten splined nut securely.
Insert Burner
Position the burner in the front of the appliance and loosely tighten the nuts on the mounting studs. The burner should be pitched downward 2° as shown in
Figures 3 and 4.
See Figure 8. Install the pedestal support kit (recommended) by attaching the 3/4” NPT flange (item a) to the bottom of the burner using the (4) #10 screws provided. Cut and thread (one end only) a 3/4” pipe nipple (item b) with length 11 inches less than dimension D in Figure 8. Thread the pipe into the flange.
Secure the burner to the appliance by tightening the nuts on the burner flange mounting studs.
Figure 8 – Burner Installed in Appliance Front
Legend
H Housing total length (CF1400 - 18”, CF2300 - 18.5”)
JCenter to bottom of housing (CF1400 - 10.88”, CF2300 - 10.5”)
KOverall housing height (CF1400 - 13.63”, CF2300 - 15.63”)
Fuel Unit By-pass Plug
Factory-Installed Pump
Bypass Plug
Failure to follow these guidelines will cause the fuel pump seals to rupture and result in oil leakage, burner malfunction and potential fire and injury hazards.
yModels CF1400 and CF2300 are shipped with the pump bypass plug installed.
yDo not remove the bypass plug from the pump. It is required for
yDo not operate the burner unless a return line or bypass loop is installed or the pump seal will rupture.
yCarefully comply with the following instructions provided in this section of the manual.
Install Oil Supply To
Specifications
Failure to properly install the oil supply system could cause oil leakage, equipment malfunction,
yCarefully install the oil supply lines, fittings and components using the guidelines provided in this section.
yThe oil supply must comply with the latest edition of NFPA 31 (Canada CSA B139) and all applicable codes.
yDo NOT install valves in the return line.
yIf the oil supply inlet pressure to the pump exceeds 3 psig or for gravity feed systems, install an oil safety or pressure reducing valve (Webster OSV, Suntec PRV or equivalent).
CF1400/CF2300 Burner Manual