Beckett CF1400 manual General Information, Hazard Definitions, Frozen Plumbing Water Damage Hazard

Page 3

Section: General Information

General Information

Hazard Definitions

Indicates a hazardous situation which, if not

avoided, will result in death or serious injury.

Indicates a hazardous situation, which, if not

avoided, could result in death, or serious injury.

Used with the safety alert symbol, indicates a

hazardous situation, which, if not avoided, may result in minor or moderate injury.

Used to address practices not related to personal injury.

Specifications

Owner’s Responsibility:

Follow these instructions exactly.

Failure to follow these instructions, misuse, or incorrect adjustment of the burner could result in asphyxiation, explosion or fire.

Contact a professional, qualified service agency for the installation, adjustment and service of your oil burning system. Thereafter, have your equipment adjusted and inspected at least annually to ensure reliable operation. This work requires technical training, trade experience, licensing or certification in some states and the proper use of special combustion test instruments.

yNever store or use gasoline or other flammable liquids or vapors near this burner or appliance.

yNever attempt to burn garbage or refuse in this appliance.

yNever attempt to light the burner by throwing burning material into the appliance.

yNever attempt to burn any fuel not specified and approved for use in this burner.

yNever restrict the air inlet openings to the burner or the combustion air ventilation openings in the room.

Frozen Plumbing and

Water Damage Hazard

Fuels

Firing Range

Motor

Ignition Trans.

Housing

Fuel Unit

Oil Nozzle

Dimensions

U.S. #1 or #2 heating oil only (ASTM D396) Canada #1 stove oil or #2 furnace oil only

DO NOT USE

GASOLINE, CRANKCASE OIL, OR ANY OIL CONTAINING GASOLINE.

CF1400 - 4.0 to 13.6 gph

CF2300 - 7.0 to 19.9 gph

CF1400:

1/2 HP 3450 rpm 120/60 Hz Standard

6.5amps @ 120 VAC

CF2300:

3/4 HP 3450 rpm 120/60 Hz Standard

12.5amps @ 120 VAC

Optional Voltages (CF1400 & CF2300): 240 VAC/1-PH,

208, 240, 480 VAC/3-PH, 50 or 60Hz

Continuous Duty, 120V/12,000V Cast aluminum

100 to 300 psig

45o to 70o Solid Refer to Figure 8.

If the facility is unattended in severely cold weather, burner primary control safety lockout, heating system component failures, power outages or other electrical system failures could result in frozen plumbing and water damage in a matter of hours. For protection, take preventive actions such as having a security system installed that operates during power outages, senses low temperature and initiates an effective action. Consult with your heating contractor or security agency.

Service Agency Responsibility:

Follow these instructions exactly.

Failure to follow these instructions could result in asphyxiation, explosion or fire.

yPlease read all instructions before proceeding. Follow all instructions completely.

yThis equipment must be installed, adjusted and started by a qualified service agency that is licensed and experienced with all applicable codes and ordinances and responsible for the installation and commission of the equipment.

yThe installation must comply with all local codes and ordinances having jurisdiction and the latest editions of the NFPA 31 and CSA-B139 & B140 in Canada.

50 Hz Motors - The burner ratings, air settings and nozzle ratings are based on standard 60 Hz motors (at 3450 rpm). Derate

all ratings 20% when using 50 Hz motors. Consult factory for specific application data.

High altitude installation - Accepted industry practice requires no derate

of burner capacity up to 2000 feet above sea level. For altitudes higher than 2000 feet, derate burner capacity 2% for each 1000 feet above sea level.

CF1400/CF2300 Burner Manual

3

Image 3
Contents To the Homeowner or Equipment Owner Potential for Fire, Smoke and Asphyxiation HazardsContents General Information Hazard DefinitionsFrozen Plumbing Water Damage Hazard Fuel Supply Oil Supply Pressure Control Required Pre-Installation ChecklistCombustion Air Supply ClearancesElectrical Supply Vent SystemVerify Burner Components Verify Firing RateVerify Air Tube Air Tube Capacity Versus Firebox Pressure± 1/8 Protect Against Stray Light Lockout Failure to follow these Mount the BurnerMount Air Tube to Burner Install NozzleCheck Electrode Settings Maintain Electrode Specifications Install Nozzle Line AssemblyDo not install valves in the return line Set Z DimensionFuel Unit By-pass Plug Factory-Installed Pump Bypass Plug Install Oil Supply To SpecificationsOne-pipe Oil System By-pass Loop Oil Supply/Return LinesBurner Fuel Flow Wire the Burner Electrical shock can cause severe personal injury or deathCan cause severe injury, death, or property damage Optional Components Typical Burner Sequence of OperationTypical Wiring 7505P Restricted Lockout Typical Burner Sequence of Operation 7184B ControlAsphyxiation, explosion or fire Tampering with, or bypassing safety controlsPrepare the Burner for Start-up Could lead to equipment malfunction and resultCF1400 Initial Indicator Adjustment Plate Settings CF2300 Initial Indicator Adjustment Plate SettingsInitial Head Position Initial Air Settings Set Appliance Limit ControlsPrepare the Fuel Unit for Air Venting Explosion and Fire Hazard Professional Service RequiredDisable Function Start the BurnerOperating the Burner Set High-fire AirSet Low-fire Air Annual Service Maintenance and ServiceReplacement Parts Annual Professional Service RequiredBurner Replacement Parts Oil Valve Mounted on Junction Box 21789U Part Name Description CF1400 Part No CF2300 Part NoSK9930 SK9936 SK9932 Limited Warranty Information