Omron NT31 NT31C Responding to Displayed Error Messages, Message Cause Remedy, Maintenance Mode

Models: NT31 NT31C

1 296
Download 296 pages 47.55 Kb
Page 245
Image 245

Responding to Displayed Error Messages

Section 7-2

 

 

 

 

NT31/NT31C Symptoms

Cause

Remedy

 

 

 

The display is dim.

Insufficient contrast or brightness

Increase the contrast/brightness (pages 191 and

 

 

193).

 

 

 

 

 

Backlight defective, or its life has

Replace the backlight (page 242).

 

expired

 

 

 

 

 

The display is too faint.

The contrast is too high.

Reduce the contrast (page 191).

 

 

 

The digits in numeral

The number of digits of a numeric

Confirm the values of the PC words allocated to the

display come out as *.

value in a numeral memory table

numeral memory table.

 

exceeds the set number.

Allocate one PC word to each numeral memory

 

 

 

 

table.

 

 

 

**” or ”***” is displayed

The numeric value in the numeral

Check the values of the PC words allocated to the

in the numeral display or

memory table exceeds the number

numeral memory table entry.

numeral input field.

of display digits.

Allocate only one word to each numeral memory

 

 

 

 

table entry if the numeral display or numeral input

 

 

field has 4 digits or less.

7-2 Responding to Displayed Error Messages

When the NT31/NT31C displays an error message, find the corresponding symptoms in the appropriate table below and respond by following the Remedy indicated in the table.

For details of the error messages displayed when using memory unit and correc- tive action to take for them, refer to 3-5 Using a Memory Unit (NT31/NT31C with Vj) in page 39 or 3-6 Using a Memory Unit (NT31/NT31C without Vj) in page 47.

7-2-1 Errors Occurring at Start of Operation and Their Remedies

The table below shows the errors that can occur when the power to the

NT31/NT31C is turned ON and when operation starts, and their remedies.

Message

Cause

Remedy

 

 

 

[No Comm. Protocol]

No communication protocol has

Using the memory switches, set the

Set the comm. Protocol by

been set.

communication method to be used for

 

communication with the host. (6-7 Setting

MAINTENANCE MODE.

Communication protocol and

Conditions for Communications with Host

 

screen data type are mismatched

 

 

by Using Memory Switches, page 157)

[Screen Data Error]

- The power was switched OFF

Initialize the screen data memory by

Screen Data corrupted.

during screen data

operation at the System Menu, then

initialization, checking, or

re-transmit the screen data. (6-4-1

Initialize Screen Memory, and download

transmission.

Clearing Screen Data, page 140)

Screen Data again.

- Transmission of screen data

If the problem persists, contact your

 

 

was interrupted.

OMRON service center.

 

- Illegal data has been written to

 

 

the screen data memory.

 

 

 

 

[No Screen Data]

No screen data is registered.

Transmit screen data from the Support

No Screen Data is saved in Screen

 

Tool.

 

 

Memory.

 

 

Download Screen Data using by the

 

 

Support Tool.

 

 

Then set the PT to the TRANSMIT

 

 

MODE, and download Screen Data

 

 

again.

 

 

235

Page 245
Image 245
Omron NT31 NT31C manual Responding to Displayed Error Messages, Errors Occurring at Start of Operation and Their Remedies