Responding to Displayed Error Messages

Section 7-2

 

 

 

 

Message

Cause

Remedy

 

 

 

[No Direct Connection Info.]

Allocated words have not been

Allocate words for the PT status control

No Direct Connection Information is set

set for the PT status control area

area and PT status notify area with the

and PT status notify area.

Support Tool and then transmit the direct

in Screen Data.

 

connection information to the

Set Direct Connecting Information in

 

 

NT31/NT31C.

Screen Data using by the Support Tool.

 

 

 

 

Then set the PT to the TRANSMIT

 

 

 

MODE and download Screen Data

 

 

 

again.

 

 

 

 

 

 

[Incorrect Screen Data]

The type of registered screen

Initialize the screen data memory, then

Screen Data in Screen Memory do not

data does not match that at the

transmit the correct screen data. (6-4-1

NT31/NT31C.

Clearing Screen Data, page 140)

match with the System Program.

 

 

 

Initialize Screen Memory, and download

 

 

 

Screen Data again.

 

 

 

 

 

 

[No Starting Screen]

No data is registered for either

Either specify a screen number for which

Specified Starting Screen is not saved.

the screen number set in the PT

data is registered at the PT status control

status control area or the Initial

area, or set the screen as the Initial

Fix Screen Data using by the Support

Screen set with the Support Tool.

Screen in the System settings under PT

Tool.

Or the screen number which

Configuration at the Support Tool.

Then set the PT to the TRANSMIT

does not exist are registered.

 

 

MODE and download Screen Data

 

 

 

again.

 

 

 

 

 

 

[Touch Panel is disconnected]

The touch panel cable (film

Contact your OMRON service center.

 

cable) inside the NT31/NT31C is

 

 

 

disconnected.

 

 

 

 

 

[Memory Switch Corrupted]

The memory switches have been

Set the memory switches again using the

Because Memory Switch setting was

initialized due to discovery of an

System Menu and the System settings

error in the memory switch

under PT Configuration at the Support

last. Initialized Memory Switch setting.

settings.

Tool. (Section 6 System Menu Operation)

Press Confirm to return to the SYSTEM

 

If the problem recurs, contact your

MENU.

 

 

OMRON service center.

 

 

 

 

 

[Calendar Data Error]

There is an error in the date/time

Check the battery voltage by checking

Calendar Data is incorrect.

values due, for example, to low

the color of the RUN LED and with the

battery voltage.

battery check in the System Menu; if the

Set to the MAINTENANCE MODE and

 

voltage is low, replace the battery with a

set Calendar Data.

 

 

new one. (Checking the Battery Voltage,

 

 

 

 

page 214, and 7-3-1 Replacing the

 

 

Battery, page 244)

 

 

If the battery voltage is confirmed to be

 

 

normal, set the calendar clock correctly

 

 

from the System Menu. (6-11-2

 

 

Displaying/Setting the Calendar and

 

 

Clock, page 195)

 

 

 

[Backup Data Error]

Initialization has been executed

Check the battery voltage by checking

Memory table and History data was

because of an error in the

the color of the RUN LED and with the

backup data area.

battery check in the System Menu; if the

initialized by backup failure.

 

voltage is low, replace the battery with a

It can be caused by lowered voltage of

 

 

new one. (Checking the Battery Voltage,

the battery.

 

 

page 214, and 7-3-1 Replacing the

 

 

 

 

Battery, page 244) The re-transmit the

 

 

memory table data from the Support Tool.

 

 

If the voltage is normal and the problem

 

 

recurs, contact your OMRON service

 

 

center.

 

 

 

[With memory switch setting screen]

Protocol settings for serial port A

Refer to Possible Combinations of

Invalid Comm. Method

and serial port B are

Communication Method Settings in page

mismatched.

158 and set the protocol of serial port A

 

 

 

and serial port B so that their settings are

 

 

matched.

 

 

* Set serial port A to None when

 

 

connecting the Support Tool and the host

 

 

at the same time.

 

 

 

 