Connecting to the Host’s RS-422A/485 Port

 

Section 5-2

 

 

 

 

 

 

 

Name

Model

Maker

Remarks

 

 

 

 

 

 

 

 

25-pin type

Delivered with the following

 

 

XM2S-2511

units:

 

 

Made by OMRON

 

 

 

C500-LK203

 

Connector

 

 

 

 

 

 

 

 

 

 

Delivered with the following

 

hood

 

 

 

 

25-pin type

units:

 

 

DB-C2-J9

 

 

Made by JAE

3G2A6-LK201-EV1

 

 

 

 

 

 

 

3G2A5-LK201-EV1

 

 

 

 

 

 

 

Cable

TKVVBS4P-03

Tachii Electric

 

 

 

Wire Co., Ltd.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.25-N3A

Japan Solderless

Recommended cable size:

 

Crimp

(fork type)

Terminal MFG

 

AWG22 to 18

 

terminals

Y1.25-3.5L

 

 

Molex Inc.

(0.3 to 0.75 mm2)

 

 

(fork type)

 

 

 

 

 

The terminal screws of the RS-422A adaptor (CPM1-CIF11) are M3 specifica- tion. When wiring, use crimp terminals for M3 use. Tighten terminal screws with a tightening torque of 0.5 N@m.

Use the same specification of the terminal screws which is used in the relay ter- minal block.

Note Always use crimp terminals for wiring.

Examples of applicable terminals

Fork type

6.2 mm or less

Round type

6.2 mm or less

5-2-7 Setting the Terminal Resistance for RS-422A/485 Communications

The serial port B connector of the NT31/NT31C has a terminal resistance setting terminal (TRM).

In RS-422A/485 communications, a terminal resistor must be set at the device at the end of the communication cable, but not at any other device.

The NT31/NT31C has a built-in terminal resistor, and whether or not the terminal resistance is applied is set by the wiring at the terminal resistance setting termi- nals (pins No. 9 and 10 of serial port B). The terminal resistance is 120 . When carrying out RS-422A/485 communications using serial port B, short between terminals No. 9 and 10 at the NT31/NT31C at the end of the RS-422A/485 cable. Leave terminals No. 9 and 10 open at NT31/NT31C units other than the one at the end of the cable.

When not using RS-422A/485 communications, the terminal resistance setting is ineffective.

In order to set the terminal resistance, wiring work is required at the cable’s con- nector: carry out the wiring correctly by referring to APPENDIX E Making the Cable, page 267.

Abbreviation

Pin number

FG

Connector

hood

 

-

Terminal resistor setting

-

-

TRM

9

RDB (+)

10

SDB (+)

11

-

12

-

 

 

-

-

25