Responding to Displayed Error MessagesSection 7-2

7-2-2 Errors Occurring during Operation and Their Remedies

The table below shows the errors that can occur during operation of the

NT31/NT31C and their remedies.

Message

Cause

Remedy

 

 

 

[Address Setting Error]

The host side allocated words

Set correct words and bits after checking the

Addressing Error exists in the

and bits set with the Support Tool

area used at the host side by referring to PC

are incorrect.

Memory Map in Appendix D of the Reference

Screen.

 

Manual or the operation manual for the PC

Correct address setting by the

 

 

being used.

Support Tool.

 

 

 

 

 

 

[Memory Table No. Error]

The memory table number set

Either increase the number of memory tables in

Memory table No. is out of limit.

with the Support Tool is outside

the System settings under PT Configuration at

the range for the number of

the Support Tool, or set the memory table

Correct the table No. by the

memory tables set in the system

number again within the established range.

Support Tool.

memory.

 

 

 

 

 

 

[Programming Console Error]

The communication settings are

Set the communication method/communication

Setting of Programming Console

incorrect.

port as follows when using the Programming

 

Console function.

Function is inadequate. It can be

 

 

S With C-series PLCs:1:1 NT Link

caused by:

 

S This PLC does not support Pro-

 

S With CS1-series PLCs:

gramming Console Function.

 

1:N NT Link (standard or high-speed)

S Protocol mismatch. Set the PLC

 

 

The PC used does not support

Not all PCs support the Programming Console

to NT Link.

the Programming Console

function. Check the model of the PC you are

S “PROGRAMMING CONSOLE”

function.

using. (6-12 Programming Console Function,

is connected to PLC.

 

page 221)

 

A Programming Console is

It is not possible to use a Programming Console

 

connected.

and the Programming Console function at the

 

 

same time. Disconnect the Programming

 

 

Console.

 

 

 

[Programming Consol Error]

The connecting cable is

Check the cable connection and perform a

Programming Console Function

defective.

conductivity test. If there is a fault, replace the

 

cable.

does not RUN. It can be caused

 

 

 

by:

Malfunction due to external noise

Carry out grounding work in accordance with the

S Connecting cable is faulty.

 

conditions by referring to 3-1-4 Grounding, page

S PROGRAMMING CONSOLE

 

34.

 

 

is connected to PLC.

A Programming Console is

It is not possible to use a Programming Console

S Protocol mismatch between the

connected.

and the Programming Console function at the

PT and PLC. Set the PLC to NT

 

same time. Disconnect the Programming

Link.

 

Console.

 

The communication conditions at

Set the communication conditions at the PC to

 

the PC have been changed in

match the conditions set in the System Menu.

 

accordance with the

 

 

NT31/NT31C Programming

 

 

Console function.

 

 

 

 