Using a Memory Unit (-Vj Versions)

 

 

Section 3-5

 

DIP Switch Functions

The functions of the DIP switches on the memory unit are indicated in the table

 

 

below.

 

 

 

 

 

 

SW1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch

 

Function

 

 

 

 

 

 

 

 

 

 

 

 

 

SW1-1

Automatic transmission (writing from the memory

OFF: Not executed

 

 

 

 

 

 

 

 

unit to the PT)

 

ON : Executed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW1-2

Automatic transmission (writing from the PT to

OFF: Not executed

 

 

 

 

 

 

 

 

the memory unit)

 

ON : Executed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW1-3

Manual transmission (Direction of transmission

OFF: Not executed

 

 

 

 

 

 

 

 

and bank used selected at the PT touch panel)

ON : Executed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF: Screen data

 

 

 

SW1-4

Data type to transfer

 

 

 

 

 

 

ON : System

 

 

 

 

 

 

 

program

 

 

SW2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch

 

 

Function

 

 

 

 

 

 

 

 

 

 

 

 

 

SW2-1

Disable/enable writing to PT

 

OFF: Disable

 

 

 

 

 

 

 

 

 

 

ON : Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW2-2

Disable/enable writing to the memory unit

OFF: Disable

 

 

 

 

 

 

 

 

ON : Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW2-3

Area (bank) selection of automatic transmission. *

OFF: Bank 0

 

 

 

 

 

 

 

 

ON : Bank 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW2-4

System/Screen simultaneous transmission

OFF: Disable

 

 

 

 

 

 

 

 

ON : Enable

 

 

 

 

 

 

 

*The memory unit stores system program or screen data for one PT in each of areas (bank 0, bank 1). (The total data storage is for two PTs.) SW2-3 sets which of these two banks is used for automatic transmission.

Reference: S The DIP switch function of the memory unit is supplemented to NT31/NT31C with the Vj suffix.

SIn the following cases, a mode setting error occurs.

More than one of the SW1-1 to SW1-3 switches are set to ON.

None of the SW1-1 to SW1-3 switches are set to ON.

SIn the following case, a protect setting error occurs.

Transmitting to the write destination has been disabled by the setting for

SW2-1 or SW2-2.

SIn the following cases, a data transmission error occurs.

An attempt is made to transmit data other than the system program to PT system program area.

An attempt is made to transmit the system program to PT screen data area.

SFor details on mode setting errors and protect setting errors, refer to Errors When Using a Memory Unit (page 45).

41