Responding to Displayed Error MessagesSection 7-2

7-2-3 Errors Occurring on Screen Data Initialization and Transmission

The table below shows the errors that can occur when the NT31/NT31C data is initialized, and during data setting and transmission, and their remedies.

 

Message

Cause

Remedy

 

 

 

[Flash Memory Error]

There is a hardware fault, or the

If the same message is displayed even after

Flash Memory I/O Error.

flash memory (memory for

clearing the screen data or transmitting screen

storing screen data) has reached

data several times, contact your OMRON

If this happens frequently, Flash

the end of its service life.

service center.

Memory may be broken.

 

 

Press Reset Switch to restart.

 

 

[Calendar Data Error]

Hardware fault, or system

Set the calendar clock again from the System

Calendar Data is incorrect.

program error

Menu. If the problem recurs, delete the program

 

in the System Installer mode, then re-install the

Set to the MAINTENANCE

 

 

program. (6-5-2 Clearing/Installing the System

MODE and set Calendar Data.

 

 

Program, page 151)

 

 

 

 

 

 

If this does not solve the problem, contact your

 

 

 

OMRON service center.

 

 

 

[Tool Transmit Error]

The connecting cable is

Check the cable connection and perform a

∗∗∗∗ Error detected while

defective.

conductivity test. If there is a fault, replace the

downloading by the following

 

cable. (Appendix F Making the Cable for

 

Connecting a PC, page 269)

case:

 

 

 

S

faulty connecting cable.

Malfunction due to external noise

Carry out grounding work in accordance with the

S

corrupted data by noise.

 

conditions by referring to 3-1-4 Grounding, page

 

34.

 

 

 

 

 

 

[Tool Transmit Error]

Malfunction due to external noise

Carry out grounding work in accordance with the

Check Sum Error occurs while

 

conditions by referring to 3-1-4 Grounding, page

 

34.

downloading by the following

 

 

 

case:

 

 

S

corrupted data by noise.

 

 

 

 

 

[Tool Transmit Error]

The connecting cable is

Check the cable connection and perform a

Time-out Error occurs while

defective.

conductivity test. If there is a fault, replace the

 

cable.

downloading by the following

 

 

 

case:

 

 

S

faulty connecting cable.

 

 

 

 

 

[Tool Transmit Error]

The receive buffer has

Retransmit the data from the Support Tool.

Reception was failed by Buffer

overflowed.

 

 

 

Over Flow Error.

 

 

 

 

 

 

238

Page 248
Image 248
Omron NT31 NT31C manual Program -5-2 Clearing/Installing the System, Case