Connecting to the Host’s RS-422A/485 Port

Section 5-2

Setting the Front Switches

Communications port 1 (RS-232C)

Communications port 2 (RS-232C/RS-422A)

I/O port selector switch

RS-232C

RS-422A

@Unit # (SW3, SW4)

Set these switches to 0.

@I/O port selection (selector switch) Set this to RS-422A.

@Communication condition setting (DIP SW1) Set this switch to OFF.

Communication is executed in accordance with the CPU bus unit system settings made at the PC. The initial values for the system settings are as follows.

-Communications speed: 9,600 bps

-Parity: Even

-Xon/Xoff control: Not executed

-Communication method: Full duplex

-Stop bits: 2 stop bits

-Data length: 7 bits

@Terminator setting (selector switch) Set this to ON.

Connecting to a CPU Unit

CVM1/CV-series (-EVj) CPUs

CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1

CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2

PC Setup

When connecting to a CVM1/CV series CPU, set the following communication conditions for the PC Setup.

Item

Setting at Host

 

 

Communications speed

Set the same speed as for the NT31/NT31C. (*1)

Stop bit

2 stop bits

 

 

Parity

Even

 

 

Data length

ASCII 7 bits

 

 

Unit #

00

*1 Set the host link communications speed at 9600 bps or 19200 bps with the Comm. Speed memory switch at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 158).

Either set PC Setup directly from a Programming Device (e.g. SYSMAC support software), or transmit the PC Setup made at a Programming Device to the CPU.

For details on the PC Setup, refer to the SYSMAC CVM1/CV500/CV1000/

CV2000 Operation Manual: Ladder Diagrams (W202-E1-j).