Omron NT31 NT31C manual 106

Models: NT31 NT31C

1 296
Download 296 pages 47.55 Kb
Page 117
Image 117

Connecting to the Host’s RS-422A/485 Port

Section 5-2

Connecting to a CVM1/CV Series Host Link Unit

CVM1/CV series rack-mounting type: CV500-LK201

A CVM1/CV series host link unit (CV500-LK201) has two connectors (commu- nication ports 1 and 2). To use the RS-422A type host link method, set commu- nication port 2 to RS-422A.

Communication port 2 is a 9-pin connector which allows selection of the RS-232C or RS-422A method. When this port is used with the RS-422A method, the I/O port selector switch on the front of the unit must be set to RS-422A (the lower position).

CPU Bus Unit Settings

When connecting to a CVM1/CV series host link unit, set the following commu- nication conditions for the CPU bus unit settings.

Item

Setting at Host

 

 

Communications speed

Set the same speed as for the NT31/NT31C. (*1)

Transfer code

ASCII, 7 data bits, 2 stop bits

 

 

Parity

Even

 

 

1-to-1/1-to-N

1-to-N(*2)

Instruction level

Level 1, 2, 3

*1 Set the host link communications speed at 9600 bps or 19200 bps with the Comm. Speed memory switch at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 158).

*1 The 1-to-N setting enables BCC (Block Check Character). It is not actually possible to connect more than one NT31/NT31C in a single host link.

Set the CPU bus unit settings directly from a Programming Device (e.g. SYS-

MAC support software).

For details on the CPU bus unit settings, refer to the SYSMAC CVM1/CV-series

Host Link Unit Operation Manual (W205-E1-j).

106

Page 117
Image 117
Omron NT31 NT31C manual 106