Omron NT31 NT31C manual Direct Connection between RS-422A Ports at Both Units

Models: NT31 NT31C

1 296
Download 296 pages 47.55 Kb
Page 128
Image 128

Connecting to the Host’s RS-422A/485 Port

Section 5-2

When connecting to the host with the memory link method, it is necessary to create a program for the memory link at the host side.

The following are the communication conditions that can be used with the memory link method. For the host (a personal computer, an FA computer, etc.), its setting should be compatible to one of the communication conditions listed in the following table. Set the same communication conditions at the NT31/NT31C by the memory switch. (page 165).

Item

Setting at Host

 

 

Input/Output board

RS-422A

 

 

Communication speed

1200, 2400, 4800, 9600, 19200, 38400 bps.

 

 

Data bits length

7 bits, 8 bits

 

 

Stop bits length

1 bit, 2 bits

 

 

Parity

None, even, odd

 

 

Flow control

None, XON/XOFF

5-2-2 Direct Connection between RS-422A Ports at Both Units

The connection method in which the RS-422A ports of an NT31/NT31C and a host are connected is described here.

 

Host link/CPU/

NT31/NT31C

Communication unit

 

 

SYSMAC

 

CS1 series PLC,

 

C series PLC,

 

CVM1/CV series

 

PLC, SRM1

25-pin

connector

Serial port B

 

 

9-pin connector or

 

 

(RS-422A, 25-pin type)

25-pin connector

 

 

 

 

RS-422A cable with connectors (max. length: 500m)

Connecting an NT31/NT31C and Host (RS-422A)

NT31/NT31C

Host

RS-422A

Wiring When Connecting a C-series Host Link Unit or CPM1 (Host Link)

Applicable units:

C200H-LK202-V1 3G2A5-LK201-EV1

117

Page 128
Image 128
Omron NT31 NT31C manual Direct Connection between RS-422A Ports at Both Units, Connecting an NT31/NT31C and Host RS-422A