Connecting to the Host’s RS-422A/485 Port

Section 5-2

Terminator (TERM):

Set to ON for termination ON.

 

Serial Communications Board

 

(Inner Board slot 1)

Terminator Switch (TERM)

Set to ON (right side).

Wire Selection Switch (WIRE)

Set to 4 (right side).

Using the NT Link (1:N) Method

Compatible Host Units

The OMRON PCs that can be connected using the RS-422A/485 type NT link (1:N) method are the CS1G/H, C200HX/HG/HE(-Z)E, and CQM1H models only. A Serial Communications Board or a communications board must be installed to make the connection.

Check the model and series of the PC against the type of CPU or communica- tions board before making the connections.

The host units that can be connected to the RS-232C port of the NT31/NT31C by the RS-422A type NT link (1:N) function via a convertor are indicated in the table below.

PC

CPUs with Built-in

CPU that becomes

 

RS-422A type

connectable by installing a

Model Name

Series

NT Link (1:N) Function

communication board

 

 

 

 

 

 

 

 

 

CS1G-CPU42/43/44/45-E(V1)

 

CS1

---

(*1)

CS1G

 

series

CS1H-CPU63/64/65/66/

CS1H

 

 

 

67-E(V1)(*1)

 

 

---

C200HE-CPU32-(Z)E(*2)

C200HE

 

C200HE-CPU42-(Z)E(*2)

(-Z)E

 

 

 

 

C200HG-CPU33-(Z)E(*2)

 

 

---

C200HG-CPU43-(Z)E(*2)

C200HG (-Z)E

 

C200HG-CPU53-(Z)E(*2)

 

 

 

 

 

C200HG-CPU63-(Z)E(*2)

 

C series

 

C200HX-CPU34-(Z)E(*2)

 

 

 

C200HX-CPU44-(Z)E(*2)

 

 

---

C200HX-CPU54-(Z)E(*2)

C200HX

 

C200HX-CPU64-(Z)E(*2)

(-Z)E

 

 

 

 

C200HX-CPU65-ZE(*2)

 

 

 

C200HX-CPU85-ZE(*2)

 

 

---

CQM1H-CPU51/61(*3)

CQM1H

*1 The serial CS1W-SCB41-E communication board is required.

*1 A C200HW-COM03-V1 or C200-COM06-V1 communication board is required. *1 A CQM1H-SCB41 Serial Communication Board is required.

Settings at the Host

C-series C200HX/HG/HE(-Z)E and CQM1H

PC Setup Area Settings

Write the communication conditions directly into the PC Setup area (data memory) using a Programming Device (e.g. CX-Programmer).

Make the setting indicated in the word shown below.

113

Page 124