Inspection and Cleaning

Section 7-4

100% cotton cloth

Hygrometer (required in some cases)

Thermometer (required in some cases)

Synchroscope (required in some cases)

Pen-writing oscilloscope (required in some cases)

Points Inspected

Inspect the following points to determine if there is any divergence from the stated criteria. If there is, either improve the surrounding environment so that the values fall within the stated range, or adjust the NT31/NT31C, for example by re-tightening screws.

Point

Inspection Details

Criterion

Inspection

Inspected

Instrument

 

 

Power supply

Fluctuation in power supply terminal

Permissible voltage fluctuation range

Tester

voltage

voltage

(24 VDC 15% to +10%)

 

 

 

 

 

Ambient

Ambient temperature (temperature in the

0 to 50_C

Thermometer

environmental

operation panel)

 

 

conditions

 

 

 

Ambient humidity (humidity in the

35% to 85% RH

Hygrometer

 

 

operation panel)

 

 

 

 

 

 

 

Presence/absence of dust

Dust must not be settled

Visual inspection

 

 

 

 

Mounting

Looseness of mounting brackets, etc.

To be no looseness

Philips screwdriver

conditions

 

 

 

Connector connections of connecting

To be fully inserted and locked, with

Philips screwdriver

 

 

cable

no looseness

 

 

 

 

 

 

Looseness of screws in external wiring

To be no looseness

Philips screwdriver

 

 

 

 

 

Conditions of external connecting cables

Faults such as incipient disconnection

Visual inspection

 

 

 

 

Components

Brightness of the backlight

Must be sufficiently bright.

Visual inspection

with limited

 

Backlight life:

 

lives

 

 

 

Brightness is halved after about

 

 

 

 

 

 

25,000 hours in use at medium

 

 

 

brightness, or about 10,000 hours in

 

 

 

use at high brightness.

 

Note 1. Do not disassemble for repairs or modification.

2.The disposal of the unit (including batteries to be disposed and backlight) may be regulated by national or local authorities. Dispose of them in accor- dance with the laws and regulations of the relevant country and local author- ity.

Reference: Desire on replacing the NT31/NT31C

When replacing the NT31/NT31C after discovering a fault during inspections, note the following points:

SBe sure to switch the power OFF before starting replacement.

SAfter replacement, check that the new NT31/NT31C is not subject to the same error.

SIf a faulty unit is returned for repairs, write as detailed a description of the fault as possible and send this description together with the unit to the OMRON ad- dress indicated on the back cover of this book.