Image 76

Connecting to the RS-232C Port at the Host

Section 4-1

When using the CQM1H’s built-in peripheral port, turn ON SW7.

Setting the Switches of a CPM2A

When using a CPM2A, the switches on the front panel must be set as shown below in order to make the PC Setup settings effective.

Set the Communications switch to OFF (down position).

Setting the Switches of a CPM2C

When using a CPM2C, the switches on the front panel must be set as shown below in order to make the PC Setup settings effective.

The settings for SW1 and SW2 depend upon the usage of the peripheral port and RS-232C port.

SConnecting PT to peripheral port

SConnecting PT to built-in RS-232C port

(A device that requires non-standard communications settings is connected to the peripheral port.)

SW1: OFF

SW2: ON

SConnecting PT to built-in RS-232C port

(A Programming Console is connected to the peripheral port.)

SW1: OFF

SW2: OFF

Setting the Switches on an RS-232C Adapter

When using a CPM1-CIF01 RS-232C Adapter, set the mode switch as shown in the following diagram.

CPM1-

CIF01 CPM1

Set the mode setting switch to HOST (upper position).