Troubleshooting

 

Section 7-1

 

 

 

 

NT31/NT31C Symptoms

Cause

Remedy

 

 

 

The graph display does

One of the percentage display

Set the 100%, 0%, and 100% values in the

not change.

settings — 100%, 0%, or 100% —

following relationship:

 

is incorrect.

100% value < 0% value < 100% value

 

 

 

The trend graph display

The cycle for graph display update

Delete other elements on the same screen as the

does not agree with the

processing is longer than the set

trend graph that are allocated to the host and have

actual time axis.

sampling cycle.

a high update frequency. Or lengthen the sampling

 

 

cycle.

 

 

 

The Programming

The communication settings are

Set the communication method as follows when

Console function cannot

incorrect.

using the Programming Console function.

be used.

 

S With C-series PLC: 1:1 NT Link

 

 

S With CS1-series PLC:

 

 

1:N NT Link (standard or high-speed)

 

 

 

 

A Programming Console is

It is not possible to use a Programming Console and

 

connected.

the Programming Console function at the same

 

 

time. Disconnect the Programming Console.

 

 

 

 

The PC does not support the

Not all PCs support the Programming Console

 

Programming Console function.

function. Check the model of PC you are using.

 

 

(6-12 Programming Console Function, page 221)

 

 

 

 

The system program for other

The Programming Console function can be used

 

vendor’s PCs has been installed.

only when the system program for OMRON PCs is

 

(PC models other than OMRON.)

installed. Install the correct system program.

 

 

 

The Device Monitor

The communications settings are not

Set the communication method as follows when

function cannot be used.

correct.

using the Device Monitor function.

 

 

S With C-series PLCs: 1:1 NT Link or 1:N NT Link

 

 

S With CS1-series PLCs:

 

 

1:N NT Link (standard or high-speed)

 

 

 

 

The PC does not support the Device

Not all PCs support the Device Monitor function.

 

Monitor function.

Check the model of PC you are using. Refer to 6-13

 

 

Device Monitor Function for details.

 

 

 

 

The system program installed in the

The Device Monitor function can be used only when

 

PT is for a PC maker other than

the PT is connected to a PT with the system

 

OMRON.

program for OMRON PCs installed. Install a system

 

 

program that supports the Device Monitor function.

 

 

 

The memory table display

Since the memory table is allocated

When the contents of the memory table are set as a

contents differ from the

to the host memory, the display is

fixed value, do not allocate the memory table to the

initial value set at the

updated in accordance with the

host.

Support Tool.

contents of the host memory.

 

 

 

 

 

 

The battery voltage has dropped and

Replace the battery and execute memory table

 

the data in the memory table has

initialization. (7-3-1 Replacing the Battery, page 244,

 

been destroyed.

and 6-4-5 Initializing the Memory Tables, page 147)

 

 

 

 

Since ON is set for the resume

Execute memory table initialization. (6-4-5

 

function, the initial values of the

Initializing the Memory Tables, page 147)

 

screen data memory are not written

If the resume function does not need to be used,

 

to the memory tables.

 

use the NT31/NT31C with the resume function OFF.

 

 

 

 

(6-9-10 Setting the Resume Function, page 181)

 

 

 

 

The numeral memory table is

Calculations are executed continuously while the PT

 

specified as the destination for a

is operating and the calculation results are

 

mathematical table’s results.

automatically written to the memory table. Specify

 

 

another numeral memory table or a word in the

 

 

host.

 

 

 

 