Troubleshooting

 

Section 7-1

 

 

 

 

NT31/NT31C Symptoms

Cause

Remedy

 

 

 

Updating of numeric

Malfunction due to external noise

Carry out grounding work in accordance with the

values and text is

 

conditions by referring to 3-1-4 Grounding, page 34.

delayed.

 

 

 

There are too many numeral/text

Reduce the number of numeral/text displays on the

 

 

 

 

displays on the displayed screen.

screen for which updating is delayed.

 

 

 

 

 

 

The cycle time is extended due to

Shorten the host cycle time.

 

 

heavy processing at the host.

 

 

 

 

 

 

 

 

In an RS-422A/485 connection,

Wire correctly by referring to Section 5 Connecting

 

 

there is illegal branching or an

to the Host from the RS-422A/485 Port.

 

 

erroneous terminator setting.

 

 

 

 

 

Some of the elements

The quantity of read data exceeds

Check the maximum number of elements by

arranged on a normal

the stipulated restriction.

referring to Display Restrictions in Appendix A of the

screen are not displayed.

 

Reference Manual. Create the screen data again

The total of the element coefficients

 

 

and then transmit all of the screen data in a batch to

 

 

for the displayed screen is greater

 

 

the NT31/NT31C.

 

 

than 1024.

 

 

 

 

 

 

 

On an overlapping screen,

Since the data is transmitted from

Check the maximum number of elements by

some of the set elements

the host in screen units, the number

referring to Display Restrictions in Appendix A of the

are not displayed.

of elements on the overlapping

Reference Manual. Create the screen data again

 

 

screen has exceeded the maximum

and then send all the screen data in a batch to the

 

 

permissible without being checked

NT31/NT31C.

 

 

by the Support Tool.

 

 

 

 

 

The System Menu cannot

Display System Menu under Change

In the System Installer mode, set Display System

be called up.

System Settings in the System

Menu to Enabled (page 153).

 

 

Installer mode is set to Disabled.

 

 

 

 

 

The following System

Screen Memory Protect under

In the System Installer mode, set Screen Memory

Menu operations are not

Change System Setting in the

Protect to Enabled (page 153).

possible.

System Installer mode is set to

 

 

-

Establishing the

Disabled.

 

 

 

 

 

 

Transmit mode

 

 

 

-

Displaying the memory

 

 

 

 

switch setting screens

 

 

 

 

Screen Memory Protect has been

Do not turn the PT power OFF during deletion of

-

Screen data memory

set to Disabled because the PT

screen data.

 

check

power supply was turned OFF during

In the System Installer mode, first change the

-

Displaying the

deletion of screen data.

setting for Screen Memory Protect to Enabled, then

 

initialization menu

 

repeat the screen data delete operation (pages 153

-

Displaying the

 

and 154)

 

 

 

 

calendar/time setting

 

 

 

 

screen

 

 

 

 

 

 

Cannot input numeric

The upper/lower (max./min.) limit

Check the screen data’s upper/lower (max./min.)

values

check for numeric value input is in

limit check setting for numeric value input, and

 

 

effect.

correct it if necessary. Refer to 2-12 Inputting

 

 

 

Numeric Values in the Reference Manual for details.

 

 

 

Cannot input numeric

Bit 5 of the PT status control area

Set bit 5 to 0 (OFF). Refer to 2-2-1 PT Status

values/character strings.

(numeral/character string input) is

Control Area (Host PT) in the Reference Manual

 

 

set to 1 (ON).

for details.

 

 

 

 

 

 

The interlock function is set for the

Inputs are prohibited in input fields when the

 

 

input field and the controlling

corresponding interlock bit is OFF. Check the status

 

 

interlock bit is OFF.

of the corresponding interlock bit and turn it ON.

 

 

 

Window screen does not

Bit 6 of the PT status control area

Set bit 6 to 0 (OFF). Refer to 2-2-1 PT Status

open

(PT window opening) is set to 1

Control Area (Host PT) in the Reference Manual

 

 

(ON).

for details.

 

 

 

Cannot switch screens

Bit 4 of the PT status control area

Set bit 4 to 0 (OFF). Refer to 2-2-1 PT Status

with touch switches

(PT screen switching) is set to 1

Control Area (Host PT) in the Reference Manual

 

 

(ON).

for details.

 

 

 

Touch switch does not

The interlock function is set for the

Touch switches are disabled when the

work. (Buzzer sounds.)

touch switch and the controlling

corresponding interlock bit is OFF. Check the status

 

 

interlock bit is OFF.

of the corresponding interlock bit and turn it ON.

234