When a fault relating to the operation of the NT31/NT31C occurs, find the symp- toms in the table below and respond by following the corresponding Remedy in- dicated in the table.

Note 1. Confirm system safety before turning the power ON/OFF or resetting.

2. Do not disassemble the PT for repair or modification.

NT31/NT31C Symptoms

Cause

Remedy

 

 

 

Power LED fails to come

Power is not being supplied.

Check the connections and make sure that power is

ON

 

supplied correctly. (3-1-3 Power Supply Connection,

 

 

page 33)

 

 

 

 

Power supply fuse has blown.

Contact your OMRON service center.

 

 

 

Nothing is displayed on

Screen No. 0 has been read at the

This is not an error. Change the screen number

the screen.

host side.

from screen number 0. (Setting the screen number

 

 

to 0 turns the screen off.)

 

 

 

 

The system startup waiting time has

This is not an error. The display will appear after the

 

not elapsed yet.

waiting time has elapsed.

 

 

 

Cannot communicate with

The Transmit mode has not been

Display the System Menu and select the Transmit

the Support Tool

established.

mode. (6-6 Transmitting the Screen Data, page 155)

 

 

 

 

Not connected to the Support Tool.

Check the installation of the connector cable. (3-2

 

 

Connecting to the Support Tool, page 35)

 

 

 

 

The PT model setting and direct

Using the PT Configuration settings of the Support

 

connection setting at the Support

Tool, set the PT model and direct connection

 

Tool do not match the NT31/NT31C.

settings that match the NT31/NT31C.

 

 

 

Cannot communicate with

Memory switch settings do not

Check the communication setting in the Memory

the host

match.

Switch menu of the Maintenance mode, and match

Cannot switch from the

 

the communication protocol settings for the host and

 

NT31/NT31C. (6-7 Setting Conditions for

system initializing screen.

 

 

Communications with Host by Using Memory

Communication error

 

 

Switches, page 157)

message is displayed

 

 

 

NT31/NT31C and host are not

Check that the type, length, and installation of the

when communicating to

the host.

correctly connected.

connector cable match the specifications. (Section 4

 

 

Connecting to the Host from the RS-232C Port, and

 

 

Section 5 Connecting to the Host from the

 

 

RS-422A/485 Port)

 

 

 

 

In an RS-422A/485 connection, the

Make the NT31/NT31C and PC termination

 

terminator setting is incorrect.

resistance settings correctly. (Section 4 Connecting

 

 

to the Host from the RS-232C Port, and Section 5

 

 

Connecting to the Host from the RS-422A/485 Port)

 

 

 

 

In an NT Link (1:N) connection, there

Make the settings again so that there is no

 

is duplication in the unit numbers.

duplication. (6-7-4 Setting the NT Link (1:N) Method

 

 

(Standard/High-speed), page 163)

 

 

 

 

The power to the NT31/NT31C,

Check the power supply.

 

NT-AL001 or host is OFF.

 

 

 

 

The buzzer has sounded

Malfunction due to external noise

Carry out grounding work in accordance with the

and the RUN LED is OFF.

 

conditions by referring to 3-1-4 Grounding, page 34.

 

 

 

 

The NT31/NT31 has developed

Contact your OMRON service center.

 

trouble.

 

 

 

 

The touch panel does not

Malfunction due to external noise

Carry out grounding work in accordance with the

respond.

 

conditions by referring to 3-1-4 Grounding, page 34.

 

 

 

 

The touch panel is broken.

Test the touch panel with I/O Check in the

 

 

MAINTENANCE MODE menu. If there is an error,

 

 

contact your OMRON service center.

 

 

 

The PC mode has

The NT31/NT31C changes the mode

This is an NT31/NT31C specification. When using a

changed to the monitor

when host link communication is

PC that can also be connected using the NT Link

mode.

used.

method, use an NT Link connection (there is no

 

 

mode change with the NT Link method).