Omron NT31 NT31C manual PC Setup, Host Model Word # Writing Value Setting

Models: NT31 NT31C

1 296
Download 296 pages 47.55 Kb
Page 123
Image 123

Connecting to the Host’s RS-422A/485 Port

Section 5-2

Connecting to a CVM1/CV-series (-EVj) CPUs

CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1

CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2

PC Setup

When connecting to the CVM1/CV series CPU by the NT link (1:1) method, no particular settings are required at the PC Setup.

Setting the Front Switches

I/O port selector switch

RS-232C

RS-422A

@Host link communication method selection (selector switch)

Set this to RS-422A.

@Communication type setting (DIP SW3) Set this switch to ON.

(for communication by NT link)

@Terminator setting (DIP SW6) Set this switch to ON.

(Set terminator ON.)

Connecting to a C-series C200HX/HG/HE(-Z)E or CQM1H

PC Setup Area Settings

Write the PC Setup area (data memory) settings directly from a Programming Device (e.g. CX-Programmer) in accordance with the host model.

Host Model

Word #

Writing Value

Setting

 

 

 

 

Port A of C200HX/HG/HE(-Z)E*1

DM6555

4000

Use NT link (1:1)

Port 2 of CQM1H*2

DM6550

4000

 

*1 RS-422A port of the communication board

*1 RS-422A port of the Serial Communications Board

For details on operations relating to the PC Setup area, refer to the manual for the PC you are using.

Setting the DIP Switches on a C200HX/HG/HE(-Z)E Communication Board Set the switches on a C200HX/HG/HE(-Z)E communication board as follows.

Switch 1: Set to 4 (4-wire type, for RS-422A)

Switch 2 : Set to ON for terminator ON (termination resistance applied)

Setting Switches on a CQM1H Serial Communications Board

Set the switches on a CQM1H Serial Communications Board as follows.

Wire selection (WIRE): Set to 4 (4-wire type, for RS-422A)

112