Omron NT31 NT31C Settings at the Host, Settings not shown here may be necessary, Switch Setting

Models: NT31 NT31C

1 296
Download 296 pages 47.55 Kb
Page 67
Image 67

 

Connecting to the RS-232C Port at the Host

Section 4-1

 

Settings at the Host

When using the host link method, the settings shown below must be made at the

 

 

host (depending on the unit, some of these settings may not be necessary, or

 

 

settings not shown here may be necessary).

 

 

 

 

 

 

 

 

Item

Switch Setting

 

 

 

 

 

 

 

 

I/O port

RS-232C

 

 

 

 

 

 

 

 

Communications speed

Set the same speed as for the NT31/NT31C. (*1)

 

 

 

Transfer code

ASCII, 7 data bits, 2 stop bits

 

 

 

 

 

 

 

 

Parity

Even

 

 

 

 

 

 

 

 

1-to-1/1-to-N

1-to-N(*2)

 

 

 

Instruction level

Level 1, 2, 3

 

 

 

 

 

 

 

 

 

Unit #

00

 

*1 Set the host link communications speed at 9600 bps or 19200 bps with the memory switch at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 160).

*2 The 1-to-N setting enables BCC (Block Check Character). It is not actually possible to connect more than one NT31/NT31C in a single host link.

The setting methods for each type of unit are described in the following.

Connecting to a C-series Host Link Unit

C200H/C200HS/C200HE/HG/HX (-Z)E Backplane mounted type:

C200H-LK201-V1

Setting the Front Switches

Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.

LK201

 

 

RUN

 

XMT

RCV

 

ERROR

 

 

 

 

 

 

 

 

SW1SW2

0 0

SW3SW4

5 2

@Unit # (SW1, SW2)

Set these switches to 0.

@Instruction level, parity, and transfer code (SW4) Set this switch to 2.

@Communications speed (SW3)

Set this switch to 5 to select 9600 bps. Set this switch to 6 to select 19200 bps.

Setting the Rear Switches

ON

@ 1-to-1/1-to-N selection (DIP switch)

CTS selector switch External

0V (ON)

1

2

3

4

Set #3 to ON.

@ CTS selection (selector switch)

Set this always to 0V (ON).