Omron NT31 NT31C manual Setup area, When using a CPM1, CPM2A, CPM2C, SRM1, When using a CQM1H

Models: NT31 NT31C

1 296
Download 296 pages 47.55 Kb
Page 120
Image 120

Connecting to the Host’s RS-422A/485 Port

Section 5-2

 

CQM1H CPUs or SRM1, set the following communication conditions for the PC

Setup area.

 

 

 

 

 

 

Item

Setting at Host

 

 

 

 

I/O port

RS-422A

 

 

 

 

Communication mode

Host link mode

 

 

 

 

Communications speed

Set the same speed as for the NT31/NT31C. (*1)

 

Stop bit

2 stop bits

 

 

 

 

Parity

Even

 

 

 

 

Data length

ASCII 7 bits

 

 

 

 

 

Unit #

00

 

*1 Set the host link communications speed at 9600 bps or 19200 bps with the Comm. Speed at the NT31/NT31C. For details, refer to Setting the Host Link Method (page 158).

Set the PC Setup area settings directly from a Programming Device (e.g. CX-

Programmer).

For details on operations relating to the PC Setup area, refer to the manual for the PC which is used.

The PC Setup area word numbers and settings to be made depending on the unit to which the connection is made are shown below.

When using port A of the communication board of C200HX/HG/HE(-Z)E

Word #

Writing Value

Settings

 

 

 

DM6555

0001

Host link mode, no CTS control

 

 

Communication conditions set by the contents of DM

DM6556

0303

Data length 7 bits, 2 stop bits, even parity,

 

 

communications speed: 9600 bps

 

0304

Data length 7 bits, 2 stop bits, even parity,

 

 

communications speed: 19200 bps

DM6558

0000

Unit # 00

When using a CPM1, CPM2A, CPM2C, SRM1

Word #

Writing Value

Settings

 

 

 

DM6650

0001

Host link mode, no CTS control

 

 

Communication conditions set by the contents of DM

 

 

 

DM6651

0303

Data length 7 bits, 2 stop bits, even parity,

 

 

communications speed: 9600 bps

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity,

 

 

communications speed: 19200 bps

 

 

 

DM6653

0000

Unit # 00

When using a CQM1H

Word #

Writing Value

Settings

 

 

 

DM6550

0001

Host link mode, no CTS control

 

 

Communication conditions set by the contents of DM

 

 

 

DM6551

0303

Data length 7 bits, 2 stop bits, even parity,

 

 

communications speed: 9600 bps

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity,

 

 

communications speed: 19200 bps

 

 

 

DM6553

0000

Unit # 00

109

Page 120
Image 120
Omron NT31 NT31C manual Setup area, When using a CPM1, CPM2A, CPM2C, SRM1, When using a CQM1H