Maintenance of the NT31/NT31C

Section 7-3

 

 

 

 

 

 

 

Error Details

Displayed Probable Cause

Remedy

 

 

 

 

 

 

 

Time-out Error

The connecting cables are not

Check the communication cable connection and

 

 

 

connected correctly. (Send/Receive)

perform a conductivity test. If there is a fault,

 

 

 

 

 

replace the cable. For details on communication

 

 

 

 

 

cables, refer to Section 4 Connecting to the Host

 

 

 

 

 

from the RS-232C Port, and Section 5 Connecting

 

 

 

 

 

to the Host from the RS-422A/485 Port.

 

 

 

 

 

 

 

 

 

 

The communication service of the

Check that the host is capable of communicating

 

 

 

host is stopped. (Send/Receive)

with the NT31/NT31C (confirm that the

 

 

 

 

 

communication settings of the host and

 

 

 

 

 

NT31/NT31C match).

 

 

 

 

 

 

 

 

 

 

Time-out Interval is too short. (Send)

Set a longer value for Time-out Interval at the host

 

 

 

 

 

side.

 

 

 

 

 

 

 

 

 

 

Time-out Interval is too short.

Set a longer value for Time-out Interval in the

 

 

 

(Receive)

System Menu. (6-9-12 Setting the Time-out Interval,

 

 

 

 

 

page 185) It may also be possible to solve the

 

 

 

 

 

problem by shortening the host cycle time.

 

 

 

 

 

 

 

PC Unit No. Error

The unit # does not match that set

Re-set the unit number at the host side to 0.

 

 

 

on the PC.

 

 

 

 

 

Noise caused data corruption during

Carry out grounding work in accordance with the

 

 

 

communication.

conditions by referring to 3-1-4 Grounding, page 34.

 

NAK received

——

Check the settings for allocated words and bits.

 

 

 

 

 

If noise is a possible factor, distance the cable from

 

 

 

 

 

sources of noise and insert a noise filter in the

 

 

 

 

 

power supply line.

 

 

 

 

 

If using the equipment in a location subject to a lot

 

 

 

 

 

of noise, use a cable with a high degree of

 

 

 

 

 

protection against noise for the transmission route.

 

 

 

 

 

Also make the cable as short as possible.

 

 

 

 

 

 

 

Undefined Command

The host is not supported.

Check the PC model used for the host.

 

Error

 

 

 

 

 

 

 

Instruction level 3 is not effective.

Check that the instruction level setting for the host is

 

 

 

 

 

 

 

 

level 1, 2, 3.

 

 

 

 

 

 

 

Data Over Flow Error

Communication command from the

Set flow control method in the host.

 

 

 

host is too long. (With memory link)

Increase transmission interval.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command transmission to the host

Check the communication cable.

 

 

 

is not possible.

Check the control method at the PT and the host.

 

 

 

 

 

 

 

 

 

 

Increase the communication on speed when it to

 

 

 

 

 

slow.

7-3

Maintenance of the NT31/NT31C

 

 

 

 

Carry out maintenance work in order to ensure that the NT31/NT31C is always

 

 

 

 

used in its optimum condition.

 

 

 

 

 

 

 

 

 

 

 

WARNING

 

 

 

 

 

Do not attempt to take the unit apart and do not touch any inter-

 

 

 

 

 

nal parts while the power is being supplied. Doing either of

 

 

 

 

 

these may result in electrical shock.

 

Spare PT

 

 

 

 

 

 

It is advisable to have a spare NT31/NT31C available to minimize system down-

 

 

 

 

time in the event of an NT31/NT31C failure or if the screen display becomes diffi-

 

 

 

 

cult to read due to deterioration of the display unit.

Backlight

 

 

When the backlight in the display is getting dim and the screen cannot be read

 

 

 

 

easily, replace the backlight. The backlight can be replaced at the rear of the

 

 

 

 

NT31/NT31C while it is mounted in an operation panel.