Programming Console Function

Section 6-12

6-12-2 Connection Method

CQM1, CQM1H, C200HX/HG/HE(-ZE), or SRM1

The connection method is exactly the same as for the NT Link (1:1). Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connect- ing to the Host from the RS-422A/485 Port for details on connecting to the PC.

*When using the Programming Console function with a CQM1H, turn ON pin 7 of the DIP switch on the front of the CQM1H’s CPU Unit.

CPM1 or CPM2A

The connection method is the same as for the NT Link (1:1). With a CPM1, con-

 

nect the RS-232C cable to the peripheral port via a CPM1-CIF01 RS-232C

 

Adapter or CPM1-CIF11 RS-422A Adapter.

 

Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5

 

Connecting to the Host from the RS-422A/485 Port for details on connecting to

 

the PC.

CPM2C

The connection method is the same as for the NT Link (1:1). Connect to the PC’s

 

communications connector with a CPM2C-CN111 or CS1W-CN114/118 Con-

 

necting Cable, a CPM1-CIF01 RS-232C Adapter, or a CPM1-CIF11 RS-422A

 

Adapter.

 

Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5

 

Connecting to the Host from the RS-422A/485 Port for details on connecting to

 

the PC.

 

* When using the Programming Console function with a CPM2C, turn ON pin 2 of

 

the DIP switch on the front of the CPM2C’s CPU Unit.

CS1G/CS1H

The connection method is exactly the same as for the NT Link (1:N) (standard or

 

high-speed). Refer to Section 4 Connecting to the Host from the RS-232C Port

 

or Section 5 Connecting to the Host from the RS-422A/485 Port for details on

 

connecting to the PC. The standard or high-speed 1:N NT Link can be used.

 

The Programming Console function can be used only when the PT’s unit num-

 

ber is set to 0. Only one unit using the Programming Console function can be

 

connected to each of the PC’s ports (built-in RS-232C port and peripheral port).

 

With the CS1G/CS1H, the Programming Console function can be used simulta-

 

neously at both the built-in RS-232C port and peripheral port. Furthermore, the

 

Programming Console function can be started at the RS-232C port while a Pro-

 

gramming Console is connected to the peripheral port.