Responding to Displayed Error Messages

Section 7-2

Example:

Parity error at serial port A

Probable Causes and Remedies

Receive Errors

The following errors can occur when receiving data.

Parity error

Framing error

Overrun error

FCS (sum value) error

Time out error

Data over flow error

PC unit No. error (host link only)

NAK received (in the case of the host link, the end code is also displayed)

Undefined command error

Send Errors

The following errors can occur when receiving data.

Time out error

Data over flow error

The remedies to take in accordance with the displayed cause are indicated in the table below.

Error Details

Displayed Probable Cause

Remedy

 

 

 

Parity Error

Communication parameters/

Check if the settings at the host for parity bit, frame

Framing Error

conditions set incorrectly.

length, communications speed, stop bit length and

 

flow control agree with those at the NT31/NT31C.

Over-run Error

 

 

 

The connecting cables are not

Check the communication cable connection and

 

 

connected correctly.

perform a conductivity test. If there is a fault,

 

 

replace the cable. For details on communication

 

 

cables, refer to Section 4 Connecting to the Host

 

 

from the RS-232C Port, and Section 5 Connecting

 

 

to the Host from the RS-422A/485 Port.

 

 

 

 

Noise caused data corruption during

Carry out grounding work in accordance with the

 

communication.

conditions by referring to 3-1-4 Grounding, page 34.

 

 

 

FCS (Check Sum) Error

Noise caused data corruption during

Carry out grounding work in accordance with the

 

communication.

conditions by referring to 3-1-4 Grounding, page 34.

 

 

 

 

The PC is transmitting incorrect

Check the operation at the host side.

 

data.

 

240

Page 250
Image 250
Omron NT31 NT31C Parity error at serial port a, Probable Causes and Remedies Receive Errors, Send Errors, Over-run Error