Using an RS-232C/RS-422A Convertor Unit

Appendix C

 

 

 

DIP Switch Settings

The convertor unit has 6 digits DIP switch for setting the RS-422A/485 communication conditions.

Before connecting the cable to the convertor unit, make the DIP switch settings.

ON

1 2 3 4 5 6

(Factory settings)

omRon NT–AL001-E

[SW1-1] Not used (always ON)

[SW1-2] Setting for built-in terminal resistance

- OFF

Terminator not set

 

- ON

Terminator set

 

[SW1-3, 4] Selection of 2-wire type/4-wire type

 

SW1-3 SW1-4

 

 

OFF

 

 

 

 

2-wire type (RS-485)

 

ON

 

 

 

 

 

 

 

 

 

 

 

SW1-3 SW1-4

 

 

OFF

 

 

 

 

4-wire type (RS-422A)

 

ON

 

 

 

 

 

 

 

 

 

 

[SW1-5, 6] Selection of the RS-422A send mode

 

SW1-5 SW1-6

 

 

OFF

 

 

 

 

Continual sending

 

ON

 

 

 

 

 

 

 

 

 

 

 

SW1-5 SW1-6

 

 

OFF

 

 

 

 

Complies with CS control of RS-232C

 

ON

 

 

 

 

(Data sent at CS high)

 

SW1-5 SW1-6

 

 

OFF

 

 

 

 

Complies with CS control of RS-232C

 

ON

 

 

 

 

(Data sent at CS low)

When using the host link or 1:1 NT Link, set the RS-422A send mode to continual sending (set both SW1-5 and 6 OFF).

When using the 1:N NT Link (standard or high-speed), set the RS-422A send mode to complies with CS control of RS-232C (i.e., one of SW1-5 and SW1-6 must be ON).

Note 1. Do not set both SW1-5 and SW1-6 ON at the same time. This may damage internal circuits.

2.The power supply to the device supplying +5 V must be turned OFF before starting wiring work.

3.Before connecting the RS-232C cable and turning on the power to an RS-232C device such as a PT (i.e., turning on the power to the convertor unit), check that the cable is wired correctly and that the DIP switch settings are correct. If the power is turned on while there is a wiring fault, the internal circuits of the convertor unit or the RS-232C device may be damaged.

4.When the convertor unit is connected to a C200HX/HG/HE (-ZE), CQM1H, CS1G/H model of OMRON PC as an RS-422A device, set DIP switches SW1-5 and SW1-6 as indicated below.

SW1-5 SW1-6

OFF ON

5 6

262