Set the unit number of the serial communication unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.

SCU21

RUN

RDY

ERC

ERH

SD1

SD2

RD1

RD2

UNIT

F

Set the unit number to 0 through F so

No.

10

that it will not overlap with the numbers

32

 

 

4

 

 

56789

used in other units.

 

 

 

Allocation DM Area Settings for CPU

Setting is written from the Programming Device (a Programming Console or CX- Programmer) directly into the allocation DM area (system setting area) of the CPU. After the setting is written, it becomes effective by turning the power ON, restarting the unit, restarting the communication port, or execution of the STUP command.

In the following, the channel numbers of the allocation DM area and settings are shown.

 

 

 

Word m = DM30000 + (100 unit number)

 

 

 

 

 

Allocation DM area (CH)

Writing

Settings

 

 

Port 1

Port 2

Value

 

 

 

 

 

 

 

 

m

m+10

8200

 

NT link (1:N) mode

 

 

 

 

 

m+1

m+11

000A

 

Communications baud rate (high-speed)

 

 

 

 

 

m+6

m+16

000j

 

j = The largest model number of the

 

connected PT (0 - 7)

 

 

 

 

 

 

 

 

 

In the memory link method, the connection can be made to a personal computer with RS-232 and an FA computer, etc.

When connecting to the host in the memory link method, it is necessary to create a program for the memory link at the host side.

The following are the communication conditions that can be used in the memory link method. For the host (a personal computer, an FA computer, etc.), its setting should be compatible to one of the communication conditions listed in the follow- ing table. Set the same communication conditions at the NT31/NT31C by the memory switch. (page 165).

Item

Settings at the host

 

 

Input/Output port

RS-232C

 

 

Communication speed

1200, 2400, 4800, 9600, 19200, 38400 bps.

 

 

Data bits length

7 bits, 8 bits

 

 

Stop bits length

1 bits, 2 bits

 

 

Parity

None, even, odd

 

 

Flow control

None, RS/CS, XON/XOFF

 

 