Lochinvar 399 - 800 Noisy, No Pump, Operation Boiler Pump, System Pump, DHW Pump, Relief Valve

Page 31

Service Manual

3Troubleshooting (continued)

Table 3E Troubleshooting Chart - Noisy System

FAULT

CAUSE

 

CORRECTIVE ACTION

 

 

 

 

 

 

- Supply gas problem. Natural gas pressures

• Refer to Section 7 - Gas Connections of the Knight

 

should be between 4 inches w.c. (1.0 kPa)

XL Installation and Operation Manual for detailed

 

and 14 inches w.c. (3.5 kPa). LP gas

information concerning the gas supply.

 

 

 

pressures should be between 8 inches w.c.

 

 

 

 

 

 

 

(2.0 kPa) and 14 inches w.c. (3.2 kPa).

 

 

 

 

 

 

 

 

 

 

 

- Gas/air mixture problem.

• Refer to the Gas Valve Adjustment Procedure

on

 

 

page 41 of this manual for the proper gas valve setting.

 

 

Verify that the vent/air intake lengths do not exceed the

 

 

maximum listed in the General Venting section of the

 

 

Knight XL Installation and Operation Manual.

 

 

 

 

 

Noisy

- Dirty/damaged burner.

• Refer to page 26 in this manual for the burner removal

 

and inspection procedure. Clean or replace the burner

Operation

 

 

as necessary.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Low water flow through the heat exchanger.

• Refer

to

Section

6 - Hydronic Piping

of

the

 

 

Knight XL Installation and Operation Manual for

 

 

minimum flow rates. Verify that the boiler is piped in a

 

 

primary/secondary fashion and that the boiler and

 

 

system pump are running on a call for heat.

 

 

 

 

 

 

 

 

- Air in the piping system.

• Properly purge all air from the piping system.

 

 

 

 

 

 

 

 

- Low system water pressure.

• Verify system pressure is a minimum of

12

psi

 

 

(82.7 kPa).

 

 

 

 

 

 

 

No Pump

- Blown fuse.

• Replace fuse F5 on the control board, see page 28 of

this manual.

 

 

 

 

 

 

 

Operation -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler Pump

- Faulty pump.

• Replace pump.

 

 

 

System Pump

 

 

 

 

 

 

 

or

- Internal fault on control board.

 

 

 

 

 

 

DHW Pump

• Replace main control board.

 

 

 

 

 

 

 

 

 

 

 

- Faulty pump relay.

• Replace relay.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- System pressure exceeds relief valve

• Lower

the

system

pressure below the

50

psi

Relief Valve

setting.

(344.7 kPa) rating of the supplied relief valve or replace

 

the standard relief valve with a higher rated valve up to

Opening

 

the maximum pressure of the heat exchanger.

 

 

 

 

• Improperly sized expansion tank.

 

 

 

 

 

 

 

 

 

 

31

Image 31 Contents
Models 399 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceMenu / Exit UP Down Knight XL displayControl inputs Control outputs Smart Control ModuleSequence of operation General OperationHow the boiler operates How the control module operatesBLR Ignition Sequence of operationBLR SH 41% Rate Use this procedure to access menus from the display panel Display panel menu accessValue will appear Display panel parameter accessParameter table Temperature DataControl Circulation Service Viewable and changeable control parameters Temperature settingsFunctions DHW settingsOutdoor air reset Data loggingMinimum SH set point Maximum air temperatureShift reset curve Maximum SH set pointAnti-cycling Boiler cascade address Control modesSH controlling sensor SH sourceCascade offset Service NotificationCirculation pumps Service technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check boiler relief valve Flue vent system and air pipingCheck water system Check expansion tankInspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settings Cleaning boiler heat exchanger Check flame signal Review with owner Check the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does Not No DisplayNo Burner OperationTemperature Resistance Checking temperature sensorsSystem Pump NoisyNo Pump Operation Boiler PumpSequence Switch/LWCOFlow FlameNo Flame Ign Anti-cyclingRunning No FlameFan Speed Low Adjustable HighLimit w/Manual Fan LowSensor Shorted Fan HighFan Speed High Sensor OpenTemp O/Shoot Open Rem Ctrl FltParameters ProgrLow 24 VAC Service BlkWatch Dog Error No Error StoredGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or ObstructionModel Gas valve adjustment procedureModels 600 Page Page KBX-SER Rev E