Service Manual
3Troubleshooting (continued)
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT | DESCRIPTION | CORRECTIVE ACTION | ||||
|
|
| ||||
| While the unit is in Service Mode, the outlet | • Establish a heating load to remove the heat from the | ||||
| temperature has exceeded 185°F. | boiler loop. |
|
|
|
|
|
| • Verify that the system is full of water and that all air | ||||
|
| has been properly purged from the system. | ||||
|
| • Verify that the boiler is piped properly into the heating | ||||
|
| system. Refer to Section 6 - Hydronic Piping of the | ||||
|
| Knight XL Installation and Operation Manual for the | ||||
|
| proper piping methods for the Knight | XL boiler. | |||
Service Blk |
| • Check voltage to the boiler pump motor on a call for | ||||
|
| |||||
|
| heat. If voltage is not present, check the wiring back | ||||
|
| to the pump relay. Replace the pump relay if | ||||
|
| necessary. |
|
|
|
|
|
| • If 120 VAC is present on a call for heat and the boiler | ||||
|
| pump is not operating, replace the pump. | ||||
|
| • Verify that the boiler pump is set to the proper speed | ||||
|
| or that the boiler pump is the proper size. Reference | ||||
|
| Section 6 - Hydronic Piping | of the Knight | |||
|
| XL Installation and Operation Manual for boiler | ||||
|
| pump specifications. |
|
|
|
|
|
|
| ||||
| 120 VAC input to the main control board has | • Check 120 VAC supply to the transformer. | ||||
| dropped below 80 VAC. |
|
|
|
|
|
Low 24 VAC |
| • Check wiring connections at the low voltage terminal | ||||
| strip. |
|
|
|
| |
|
| • Check the wire size/length to remote devices. | ||||
|
| • Replace the transformer. |
|
|
|
|
Watch Dog Error | The main control board has detected an | • Replace the main control board. |
|
|
|
|
internal fault. |
|
|
|
|
| |
|
|
|
|
|
|
|
Write EEProm | The main control board has detected an | • Replace the main control board. |
|
|
|
|
internal fault. |
|
|
|
|
| |
|
|
|
|
|
|
|
| The main control board has detected an | • Replace the main control board. |
|
|
|
|
CRC Parameters | internal fault. |
|
|
|
|
|
|
|
| ||||
| The main control board has detected an | • Press the ENTER/RESET button on the SMART | ||||
No Error Stored | internal fault. | SYSTEM display panel. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|