Service Manual
3Troubleshooting (continued)
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT | DESCRIPTION |
| CORRECTIVE ACTION |
| ||||
|
|
| ||||||
| The outlet water temperature has exceeded | • Verify that the system is full of water and that all air | ||||||
| the setting of the high limit. | has been properly purged from the system. |
| |||||
|
| • Verify that the boiler is piped properly into the heating | ||||||
|
| system. Refer to Section 6 - Hydronic Piping of the | ||||||
|
| Knight | XL | Installation | and Operation | Manual | ||
|
| for the proper piping methods for the Knight XL. | ||||||
|
| • Check voltage to boiler pump motor on a call for | ||||||
|
| heat. If voltage is not present, check wiring back to | ||||||
Adjustable High |
| the pump relay. |
|
|
|
| ||
| • Replace the pump relay if necessary. |
|
| |||||
Limit w/Manual |
|
|
| |||||
|
|
|
|
|
|
|
| |
Reset |
| • If 120 VAC is present on a call for heat and the boiler | ||||||
(will require a manual |
| pump is not operating, replace the pump. |
|
| ||||
reset once the condition |
| • If the system pump is a variable speed pump, ensure | ||||||
has been corrected. Press |
| |||||||
| that the system flow is not less than the boiler flow. | |||||||
the RESET button on the |
| |||||||
| • If operating on either an inlet or system supply sensor, | |||||||
SMART SYSTEM display |
| |||||||
| check temperature setting of the main control board. | |||||||
to reset.) |
| |||||||
|
|
|
|
|
|
|
| |
|
| • If the high limit has tripped, check setting of the | ||||||
|
| device. |
|
|
|
|
|
|
|
| • Check resistance of water sensors and compare to | ||||||
|
| Table 3B on page 30 of this manual. Replace sensor | ||||||
|
| if necessary. |
|
|
|
| ||
|
| • Replace high limit. |
|
|
|
| ||
|
|
| ||||||
| The actual fan RPM is 30% lower than what | • Vent/air intake lengths exceed the maximum allowed | ||||||
| is being called for. | lengths. Refer to Section 3 - General Venting of the | ||||||
|
| |||||||
Fan Low |
| Knight | XL | Installation | and Operation | Manual for | ||
| proper lengths. |
|
|
|
| |||
OR |
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
Fan Speed Low |
| • Check | for | obstruction | or | blockage in | the | vent/air |
(will require a manual |
| |||||||
| intake pipes or at terminations. |
|
| |||||
reset once the condition |
|
|
| |||||
|
|
|
|
|
|
|
| |
has been corrected. Press |
| • Check the wiring connections at the fan and at the | ||||||
the RESET button on the |
| |||||||
| main control board. |
|
|
|
| |||
SMART SYSTEM display |
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
to reset.) |
| • Replace the fan. |
|
|
|
| ||
|
|
|
|
|
| |||
|
| • Replace the main control board. |
|
| ||||
|
|
| ||||||
| Blown fuse. | • Replace fuse F4 on the control board, see page 28 of | ||||||
|
| this manual. |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
35