Service Manual
3Troubleshooting
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT | DESCRIPTION | CORRECTIVE ACTION |
|
| Outlet water temperature has exceeded the | • Verify that the boiler pump is set to the proper speed | |
Temp O/Shoot | maximum outlet water temperature. | or that the boiler pump is the proper size. Reference | |
| Section 6 - Hydronic Piping of the Knight | XL | |
(continued) |
| Installation and Operation Manual for boiler pump | |
|
| specifications. |
|
|
| • Replace the main control board. |
|
|
|
|
|
| External control is cycling too often. | • Check set point of the external control. |
|
Rem Ctrl Flt |
| • Check the wiring between the external control and the | |
| unit. |
| |
|
|
| |
|
| • Replace the control. |
|
|
|
| |
Parameters | After downloading parameters from a laptop, | • Press the ENTER/RESET button on the SMART | |
the main control board must be reset. | SYSTEM display panel. |
| |
Progr |
|
| |
|
|
| |
(will require a manual |
|
|
|
reset once the condition |
|
|
|
has been corrected. Press |
|
|
|
the RESET button on the |
|
|
|
SMART SYSTEM display |
|
|
|
to reset.) |
|
|
|
|
|
|
|
APS | Air pressure switch contacts are open. | • Check the wiring connections to switch. Wires should | |
| |||
| be connected to the common and normally closed | ||
Open |
| ||
| terminals. |
| |
(will require a manual |
|
| |
|
|
| |
reset once the condition |
| • Vent/air intake lengths exceed the maximum allowed | |
has been corrected. Press |
| ||
| lengths. Refer to Section 3 - General Venting of the | ||
the RESET button on the |
| ||
| Knight XL Installation and Operation Manual | for | |
SMART SYSTEM display |
| ||
| proper lengths. |
| |
to reset.) |
|
| |
|
|
| |
|
| • Check for obstruction or blockage in the vent/air | |
|
| intake pipes or at terminations. |
|
|
| • Check reference hoses connected to the air pressure | |
|
| switch for blockage or obstruction. |
|
|
| • Inspect the burner. Reference page 26 of this manual | |
|
| for removal and cleaning procedures. Replace if | |
|
| necessary. |
|
|
| • Inspect the heat exchanger. Reference page 27 of this | |
|
| manual for removal and cleaning procedures. | |
|
| Replace if necessary. |
|
|
| • Faulty air pressure switch. Replace switch. |
|
|
|
|
|
38