Bradford-White Corp Residential Gas-Fired Hydronic Boilers, BJVS Special Precautions for LP Gas

Page 11

Brute Mini Hydronic Boiler

Page 11

 

 

Distance

 

 

Boiler Size

 

 

 

 

 

 

 

 

From Gas

50

75

100

125

160

225

Meter

 

 

 

 

 

 

 

 

Pipe Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0-50'

1/2

3/4

3/4

3/4

1

1

0-15m

 

 

 

 

 

 

50-100'

3/4

3/4

3/4

1

1

1-1/4

15-30m

 

 

 

 

 

 

100-200'

3/4

1

1

1

1-1/4

1-1/4

30-60m

 

 

 

 

 

 

*Note: These figures are for Natural Gas (.65 Sp. Gr.), and are based on 1/2" water column pressure drop. Check supply pressure with a manometer, and local code requirements for variations. For LPG, reduce pipe diameter one size, but maintain a 1/2" minimum diameter. A 'normal' number of Tees and elbows have been taken into allowance.

Table 4. Natural Gas Pipe Size Requirements*

Gas Supply

 

Inlet

 

Tee

To Equipment

Inlet

Fitting

 

3 in.

Nipple

(76mm) Min.

 

 

Cap

Figure 5. Typical design for a sediment trap/drip leg.

4.A sediment trap (drip leg) must be installed ahead of the gas controls (see Figure 5). Fit the trap with a threaded cap which can be removed for cleaning.

5.Install a manual gas shutoff valve for service and safety. Do not use a restrictive gas cock. Flexible gas connectors, if used, must be CSA rated for the total input rating of the boiler.

6.Disconnect the boiler and its individual shutoff valve from the gas supply system during pressure testing of the system at pressures higher than 1/2 pounds per square inch (psi) (3.45 kilopascals [kPa]). If the test pressure is equal to or less than 1/2 psi (3.45 kPa), close the manual shutoff valve on the heater during the piping pressure test.

7.If the gas supply pressure is less than required, check for undersized pipe between the meter and the boiler, a restrictive fitting, or an undersized gas meter. Gas supply pressures to the heater are listed in Table 5.

NOTE: The maximum inlet gas pressure must not exceed the specified value. The minimum value listed is for the purpose of input adjustment. Refer to Table 5.

Supply Pressure

Minimum

Maximum

 

 

 

Natural Gas

5.5 Inches WC

10.5 Inches WC

 

(1.3 kPa)

(2.5 kPa)

 

 

 

LP Gas

10.0 Inches WC

13.0 Inches WC

 

(2.4 kPa)

(3.1 kPa)

Table 5. Gas Supply Pressure Requirements.

NOTE: The boiler and all other gas appliances sharing the boiler gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. Low gas pressure could be an indication of an undersize gas meter and/or obstructed gas supply line.

8.The correct high fire burner manifold gas pressure is stamped on the rating plate. The regulator is pre-set at the factory, and normally requires no further adjustment. For two-stage units (BJVS 100-225) be sure unit is able to fire at both high and low fire.

9.Before operating the boiler, the complete gas supply system and all connections must be tested for leaks using a leak detector solution. Do not use an open flame.

Caution

Some leak test solutions (including soap and water) may cause corrosion or stress cracking. Rinse the piping with water after testing.

Attention

Certaines solultions d’essai d’étanchéité (y compris l’eau et le savon) peuvent causer de la corrosion ou de la fissuration. Rincez les tuyaux à l’eau apprès l’essai d’étanchéité.

4.2 Special Precautions for LP Gas

LP Gas is heavier than air and can therefore more readily collect or “pool” in enclosed areas if provision for proper ventilation is not made. Be sure to pay special attention to proper ventilation for LP gas. Locate boilers a safe distance from LP gas cylinders and filling equipment. In the United States, consult the “National Fuel Gas Code” (NFPA 54 / ANSI Z223.1, latest edition) or in Canada, the Propane Installation Code (CSA-B149.1), any local codes and fire protection authorities about specific installation restrictions in your area.

Image 11
Contents Brute Mini Table of Contents General Information General Specifications Installation InstructionsSpecifications Diagnostic ToolsBjvt models, the damper plate hole should never be blocked Field AssemblyFlooring ClearancesExhaust Venting VentingCombustion Air Supply Venting Multiple Appliances Vent Pipe Sizing and General InstallationCommon Venting Systems Inspection of Commonly Vented Appliances Gas Supply and Piping Gas ConnectionsTypical design for a sediment trap/drip leg Special Precautions for LP GasAlternate Auto-Bypass Operation Adjusting the bypassWater Connections Water PipingTypical Plumbing Installations Multi-Zone Damage from improper flow is not warranted Flow RequirementsOxygen Permeable Systems Main PowerElectrical Chilled Water SystemsWiring Diagram, Spark Ignition System Bjvs 50 Wiring Diagram, Standing Pilot System Bjvt Wiring Diagram, Spark Ignition, Two-Stage Bjvs Multiple Zone Wiring Normal Operation Operating InstructionsGrounding Auxiliary DevicesBoiler Start-up Start-upFilling the System Lighting the Boiler Lighting and Shutdown ProceduresComplete Shutdown High Altitude Burner Air Shutter AdjustmentShutdown Main Burner Shutdown Bjvt only General Maintenance MaintenanceBoiler Components and Their Operation General Boiler Troubleshooting TroubleshootingSymptom Cause Remedy Troubleshooting GuideStart Troubleshooting Honeywell S8600 Intermittent Pilot SystemGlossary of Terms Electrical TroubleshootingGlossary Ordering Information Replacement PartsParts List BJVS-50 BJVT-50 BJVS-75 BJVT-75 Jacket and Fire Box Components Parts Identification 11.3Exploded ViewBrute Mini Hydronic Boiler H2343000