Bradford-White Corp BJVT, BJVS warranty Troubleshooting Guide, Symptom Cause Remedy

Page 28

Page 28BRADFORD WHITE CORP.

9.2

Troubleshooting Guide

 

#

Symptom

Cause

Remedy

1.

Pump not

A. No power

A. Check circuit breakers and power source.

 

operating

B. Pump defective

B. Replace.

 

 

C. Incorrectly wired

C. Recheck wiring diagrams.

2.

Pilot outage

A. Inlet gas pressure too low

A. Consult gas utility company. Inlet gas pressure to boiler

 

 

 

should be 5.5" to 10.5" water column on natural gas. 0.0" to

 

 

B. Inlet gas pressure too high causing

13.0" on propane gas.

 

 

B. Pressure should be regulated within limits shown above.

 

 

an unstable blowing pilot

C. Replace thermocouple.

 

 

C. Weak or defective thermocouple

 

 

D. Damaged pilot or thermocouple

D. Replace.

 

 

E. Dirty pilot

E. Blow dust or lint out of pilot.

 

 

F. Plugged or undersized pilot orifice

F. Clean or replace pilot orifice.

3.

Flame roll-out

A. Blocked flue

A. Remove blockage.

 

on start-up

B. Pilot out of position (delayed ignition)

B. Correct pilot position.

 

 

C. Blocked heat exchanger or flue

C. Clean and correct as necessary.

 

 

D. Refractory tile out of place

D. Correct or replace tile as necessary.

 

 

E. Altered draft diverter

E. Install factory-provided draft diverter.

4.

Spillage at

A. Cold chimney

A. Allow boiler to operate 5 minutes to create draft action.

 

draft hood

B. Vent pipe pitches down to chimney

B. Reinstall vent pipe to pitch up from boiler to chimney.

 

 

C. Blocked chimney

C. Remove blockage.

 

 

D. Draft hood altered

D. Install factory-provided draft diverter.

 

 

E. Pre-fabricated chimney with incorrect cap

E. Install U.L. listed vent cap.

5.

Flame has

A. Low primary air

A. Correct manifold pressure according to rating plate. Correct

 

lazy yellow tip

 

orifice size if necessary (see parts list). Clean burner ports if

 

 

 

dirty. Verify correct fuel type.

6.

Not enough heat

A. Inadequate gas supply

A. Gas meter too small. Gas line from meter to boiler too small.

 

 

B. Low manifold gas pressure

B. Gas pressure on boiler manifold (at normal firing rate)

 

 

 

should be adjusted to 4.0"W.C. natural gas, 9.0"W.C.

 

 

C. Boiler size inadequate

propane.

 

 

C. Replace with boiler of higher input.

 

 

D. BJVS 100-225 only - Boiler not going

D. Check operation and setting of two-stage operating control.

 

 

to high fire.

 

7.

Pump noisy

A. Air in volute

A. Bleed air from volute. Check pump alignment.

 

 

B. Worn coupling or bearings

B. Replace worn parts.

8.

Boiler pounding

A. Too low water flow through boiler

A. Check temperature rise between inlet and outlet boiler piping.

 

or knocking

 

15°F to 25°F temperature rise is recommended. If temperature

 

 

 

rise is over 25°F, increase pipe size or pump capacity or

 

 

 

locate obstruction. Check for stuck closed zone valves.

 

 

 

Check for zone pumps not operating. Check for closed valve

 

 

 

in system.

9.

Boiler condensing

A. Low water temperature

A. Flue product moisture will condense at the start-up until the

 

 

 

boiler water temperature reaches the normal operating

 

 

 

conditions.

10.

Pump cavitates

A. Defective fill valves or pressure regulator

A. Replace.

 

or low water

B. Oversized expansion tank

B. Replace.

 

pressure at boiler

C. Expansion tank piped incorrectly

C. Repipe expansion tank to suction size of pump.

 

gauge or bubbles

 

 

 

in system at high

 

 

 

temperature

 

 

11.

Pressure relief

A. Water-logged expansion tank

A. Drain 2/3 of the water from the expansion tank.

 

valve opens

 

 

12.

Pilot is lit but main

A. Gas valve not at "on" position (BJVT)

A. Turn knob to "on" position.

 

burners will not

B. Boiler off on hi-limit control

B. Check for low water flow or hi-limit setting.

 

come on

C. Boiler incorrectly wired

C. On single or multiple zone systems with zone valves, room

 

 

 

thermostat should be wired to R & W terminals. For multiple

 

 

 

zone systems with zone pumps, thermostats for extra zones

 

 

D. Boiler off on blocked vent switch

should be wired to R & A terminals.

 

 

D. Remedy as in symptom #4. Reset the manual reset switch.

 

 

E. Boiler off on flame roll-out switch

E. Remedy as in symptom #3. Reset the manual reset switch.

 

 

F. Broken wire in thermostat circuit

F. Check continuity through thermostat circuit with wires

 

 

or defective thermostat

disconnected from R & W.

 

 

G. BJVS 100-225 Only - Two-stage operating

G. Check continuity and operation through two-stage

 

 

control not functioning or loose contact.

operating control.

 

 

 

 

13.

Boiler short cycles

A. Heat anticipator in room thermostat

A. Increase setting (0.8 - 1.0 is usually satisfactory).

 

 

set too low

B. Increase size of pump or increase piping size.

 

 

B. Low water flow through boiler

 

 

C. Hi-limit switch may be set too low

C. Increase setting to at least 20°F over outlet water temperature.

 

 

 

 

Table 8. Troubleshooting Guide.

Image 28
Contents Brute Mini Table of Contents General Information Installation Instructions SpecificationsDiagnostic Tools General SpecificationsField Assembly Bjvt models, the damper plate hole should never be blockedClearances FlooringCombustion Air Supply VentingExhaust Venting Common Venting Systems Vent Pipe Sizing and General InstallationVenting Multiple Appliances Inspection of Commonly Vented Appliances Gas Connections Gas Supply and PipingSpecial Precautions for LP Gas Typical design for a sediment trap/drip legAdjusting the bypass Water ConnectionsWater Piping Alternate Auto-Bypass OperationTypical Plumbing Installations Multi-Zone Flow Requirements Damage from improper flow is not warrantedMain Power ElectricalChilled Water Systems Oxygen Permeable SystemsWiring Diagram, Spark Ignition System Bjvs 50 Wiring Diagram, Standing Pilot System Bjvt Wiring Diagram, Spark Ignition, Two-Stage Bjvs Multiple Zone Wiring Operating Instructions GroundingAuxiliary Devices Normal OperationFilling the System Start-upBoiler Start-up Lighting and Shutdown Procedures Lighting the BoilerShutdown Main Burner Shutdown Bjvt only High Altitude Burner Air Shutter AdjustmentComplete Shutdown Maintenance General MaintenanceBoiler Components and Their Operation Troubleshooting General Boiler TroubleshootingTroubleshooting Guide Symptom Cause RemedyTroubleshooting Honeywell S8600 Intermittent Pilot System StartGlossary Electrical TroubleshootingGlossary of Terms Parts List Replacement PartsOrdering Information BJVS-50 BJVT-50 BJVS-75 BJVT-75 Jacket and Fire Box Components 11.3Exploded View Parts IdentificationBrute Mini Hydronic Boiler H2343000