9.3 Troubleshooting Honeywell S8600 Intermittent Pilot System

Some boilers may be equipped with an ignition module that shuts off pilot gas if pilot fails to light.

Start

Turn off gas supply.

Turn thermostat

(controller) to call for

heat.

Power to module

(24V nominal).

￿YES

Spark across igniter/

sensor gap.

￿YES

Turn gas supply on. Pilot burner lights?

￿YES

Spark stops when pilot

is lit?

￿YES

Main burner lights?

￿YES

System runs until call

for heat ends?

￿YES

Call for heat ends. System shuts off?

￿YES Troubleshooting ends

To reset, interrupt power to heater

Note: Before troubleshooting, familiarize yourself with the start-up and checkout procedure.

￿

Check line voltage power, low voltage transformer, hi- limit switch,

 

 

 

NO

thermostat (controller) and wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pull ignition lead and check spark at module.

 

 

 

 

NO

Spark okay?

 

 

 

 

 

 

 

 

 

 

 

 

 

￿

 

 

 

￿YES

 

 

 

 

 

 

 

 

 

 

 

Check ignition cable ground wiring, ceramic insulator and gap, and correct.

 

 

 

 

Check boot of the ignition cable for signs of melting or buckling. Take

 

 

 

 

 

protective action to shield cable and boot from excessive temperatures.

 

 

 

 

 

 

 

 

 

￿

Check that all manual gas valves are open, supply tubing and pressures

 

 

 

 

are good, and pilot burner orifice is not blocked.

 

 

Check electrical connections between module and pilot operator on gas

 

 

 

NO

 

 

 

 

control.

 

 

 

 

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is

 

 

 

 

 

 

 

 

 

okay, replace gas valve; if not, replace module.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Check continuity of ignition cable and ground wire.

 

 

 

 

 

 

Clean flame rod.

 

 

￿

Check electrical connections between flame rod and module.

 

 

 

 

 

Check for cracked ceramic flame rod insulator.

 

 

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

 

 

Adjust pilot flame.

 

 

 

 

If problem persists, replace module.

￿

 

 

 

 

 

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace

 

 

 

NO

 

 

 

 

module.

 

 

 

 

Check electrical connections between module and gas valve. If okay,

 

 

 

 

 

 

 

 

 

replace gas valve.

 

 

 

 

 

 

 

 

 

 

 

 

￿

Check continuity of ignition cable and ground wire.

 

 

 

 

NO

 

 

 

 

Note: If ground is poor or erratic, shutdowns may occur occasionally even

 

 

 

 

 

though operation is normal at the time of checkout.

 

 

 

 

 

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace module.

 

￿

 

 

Check for proper thermostat (controller) operation.

 

NO

 

Remove MV lead at module; if valve closes, recheck temperature

 

 

 

 

 

controller and wiring; if not, replace gas valve.

 

 

Repeat procedure until trouble-free operation is obtained.

Image 29
Contents Brute Mini Table of Contents General Information Specifications Installation InstructionsDiagnostic Tools General SpecificationsBjvt models, the damper plate hole should never be blocked Field AssemblyFlooring ClearancesExhaust Venting VentingCombustion Air Supply Venting Multiple Appliances Vent Pipe Sizing and General InstallationCommon Venting Systems Inspection of Commonly Vented Appliances Gas Supply and Piping Gas ConnectionsTypical design for a sediment trap/drip leg Special Precautions for LP GasWater Connections Adjusting the bypassWater Piping Alternate Auto-Bypass OperationTypical Plumbing Installations Multi-Zone Damage from improper flow is not warranted Flow RequirementsElectrical Main PowerChilled Water Systems Oxygen Permeable SystemsWiring Diagram, Spark Ignition System Bjvs 50 Wiring Diagram, Standing Pilot System Bjvt Wiring Diagram, Spark Ignition, Two-Stage Bjvs Multiple Zone Wiring Grounding Operating InstructionsAuxiliary Devices Normal OperationBoiler Start-up Start-upFilling the System Lighting the Boiler Lighting and Shutdown ProceduresComplete Shutdown High Altitude Burner Air Shutter AdjustmentShutdown Main Burner Shutdown Bjvt only General Maintenance MaintenanceBoiler Components and Their Operation General Boiler Troubleshooting TroubleshootingSymptom Cause Remedy Troubleshooting GuideStart Troubleshooting Honeywell S8600 Intermittent Pilot SystemGlossary of Terms Electrical TroubleshootingGlossary Ordering Information Replacement PartsParts List BJVS-50 BJVT-50 BJVS-75 BJVT-75 Jacket and Fire Box Components Parts Identification 11.3Exploded ViewBrute Mini Hydronic Boiler H2343000