Crown Boiler BWC Series installation instructions Air for Ventilation

Page 7

WARNING

OUTDOOR COMBUSTION AIR MUST BE PIPED TO THE AIR INTAKE. NEVER PIPE COMBUSTION AIR FROM AREAS CONTAINING CONTAMINATES SUCH AS SWIMMING POOLS AND LAUNDRY ROOM EXHAUST VENTS. CONTAMINATED COMBUSTION AIR WILL DAMAGE THE BOILER AND MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.

V Air for Ventilation

Air for combustion must always be obtained directly from outdoors, however sufficient air for ventilation must still be provided in the boiler room. Air for ventilation is required to keep various boiler components from over- heating and is always obtained from indoors. To ensure an adequate ventilation air supply, perform the following steps:

Step 1: Determine whether the boiler is to be installed in a confined space - A confined space is defined by the National Fuel Gas Code as having a volume less than 50 cubic feet per 1000 BTU/hr input of all appliances installed in that space. To determine whether the boiler room is a confined space:

1)Total the input of all appliances in the boiler room in thousands of BTU/hr. Round the result to the next highest 1000 BTU/hr.

2)Find the volume of the room in cubic feet. The volume of the room in cubic feet is: Length (ft) x width (ft) x ceiling height (ft)

In calculating the volume of the boiler room, consider the volume of adjoining spaces only if no doors are installed between them. If doors are installed between the boiler room and an adjoining space, do not consider the volume of the adjoining space, even if the door is normally left open.

3)Divide the volume of the boiler room by the input in thousands of BTU/hr. If the result is less than 50, the boiler room is a confined space.

Example:

A BWC225 and a water heater are to be installed in a room measuring 6ft – 3 in x 7ft with an 8 ft ceiling. The water heater has an input of 30000 BTU/hr:

Total input in thousands of BTU/hr = (225000 BTU/hr + 30000 BTU/hr) / 1000 = 255 MBTU/hr Volume of room = 6.25 ft x 7 ft x 8 ft = 350 ft3

350/255 = 1.37. Since 1.37 is less than 50, the boiler room is a confined space.

Step 2a: If the boiler is to be placed in a confined space, provide two openings into the boiler room, one near the floor and one near the ceiling. The top edge of the upper opening must be within 12” of the ceiling and the bottom edge of the lower opening must be within 12” of the floor (Fig 5.1). The minimum opening dimension is 3 inches.

If the BWC boiler is the only gas-burning appliance in the boiler room, these openings must each have a minimum free area of 100 square inches.

If other gas-burning appliances are in the boiler room, size the openings in accordance with the appliance manufacturer’s instructions or the National Fuel Gas Code. Minimum opening free area is 100 square inches even if opening requirements for other appliances are less.

5

Image 7
Contents BWC Series Page VII II Specifications Product DescriptionIV Locating the Boiler III Before InstallingMinimum Clearance To Combustible Material Air for Ventilation Page Vent System Design VI VentingHorizontal Direct Venting Vent Options 1,2 2a Summary of Horizontal Venting Options 3c Positioning Vent Terminal Under Overhangs Vertical Direct Vent System Vent Options 6 2b Summary of Vertical Venting Options VENT/ AIR Intake Fitting Equivalent Length Removing an Existing Boiler From a Common Chimney Vent / Intake System Assembly7a STAR-34 Connection to Vent Collar Z-VENT III Connection to Vent Collar SAF-T Vent Ezseal Connection to Vent Collar 10 Fasnseal Connection to Vent Collar 11 Condensate Piping Arrangement Gas Connection To Boiler VII Gas PipingViii System Piping General System Piping PrecautionsSystem Design Method 1 Primary/Secondary Piping Boiler in Secondary Loop Piping Method #1 Heat Only 4a Piping Method #1 Secondary Loop Piping Shaded Pipe and Circulator Sizing for Boiler Loop Fitting Equivalent Lengths Method 2 Primary/Secondary Piping Boiler in Primary Loop Piping Method #2 Heat Only 10a Piping Method #2 Secondary Loop Piping Bolded Page Flow GPM Piping for Special Situations 14 Chiller Piping IX Wiring Wiring Connections Diagram Ladder Diagram Page Start-up and Checkout BWC Series Lighting and Operating Instructions For Your Safety Read Before LightingBWC Burner Typical CO2/O2 Combustion Readings Gas Valve DetailPage XI Operation Normal Display In Standby ModePage 170 First Digit Boiler Status Boiler StatusOutdoor Reset Curve Continuously XII. Service and MaintenancePage No Error Code Displayed XIII. TroubleshootingCode Condition Possible Causes Soft Lockout Codes DisplayedHard Lockout Codes Displayed XIV Parts BWC Replacement Parts List TBD Page Page Page Page Ignition Electrode Gasket, 5mm 240011 Page BWC Replacement Parts List Page Page Page Page Page PN 980040 BWC 08/05

BWC Series specifications

The Crown Boiler BWC Series is a modern choice for heating needs, renowned for its efficiency and robust design. This series offers a range of residential and light commercial heating applicabilities, ensuring both comfort and reliability for users.

One of the standout features of the BWC Series is its efficiency. Crown Boilers utilize advanced technologies to maximize energy output while minimizing fuel consumption. With an AFUE (Annual Fuel Utilization Efficiency) rating often exceeding 90%, users can expect significant cost savings on their energy bills over time.

The BWC Series employs a high-quality, stainless steel heat exchanger, which not only enhances performance but also extends the lifespan of the boiler. This heat exchanger is designed to transfer heat efficiently, ensuring that the maximum amount of energy from the fuel is converted into usable heat. Additionally, the design helps to prevent corrosion and maintain system integrity over years of usage.

For technological advancements, the BWC Series incorporates a modulating gas valve which allows for precise control over the boiler's operation. This feature enables the system to adjust its output based on the heating demands of the home, resulting in improved energy efficiency and consistent comfort levels. Moreover, this modulating technology reduces the frequency of cycling, thereby prolonging the lifespan of the unit and minimizing wear and tear.

Another characteristic of the Crown Boiler BWC Series is its user-friendly interface. The boiler is equipped with a simple control panel that allows for easy monitoring and adjustment of settings. This accessibility is essential for users who want to manage their heating system without the need for extensive technical knowledge.

In terms of installation and maintenance, the BWC Series is designed with convenience in mind. Its compact footprint allows it to fit comfortably in a variety of spaces, making it an ideal choice for homes with limited installation areas. Additionally, Crown Boiler's commitment to high manufacturing standards ensures that the units require minimal maintenance, providing peace of mind to homeowners.

Overall, the Crown Boiler BWC Series is an excellent solution for those seeking efficient, reliable heating. Its combination of advanced technology, quality construction, and user-friendly design makes it an attractive option for any residential or light commercial application. Whether replacing an old system or installing a new one, the BWC Series delivers comfort and performance that can be depended upon.