OWNER’S MANUAL
INSTALLATION
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible ma- terial clearances, you must also meet re- quired clearances between fireplace open- ings and mantel shelf on each side of the fireplace. If you do not meet the clearances listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel shelf and top of fireplace opening, a
10"
8"
6"
2 1/2"
Minimum Non- |
|
| (A) | |
| ||||
Combustible | ||||
| ||||
Material |
| |||
|
|
| 12" | |
|
|
|
|
Mantel Shelf
18" |
| 20" | 22" |
| |||
|
|
|
|
Underside of
Mantel Shelf
All minimum distances are in inches
24"
Top of Fireplace
Opening
hood is not required (see Figure 6).
Determining Minimum Mantel Clearance When using a Hood
If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clear-
Minimum Non- | Distances to |
Combustible | Underside of |
Material Height | Mantel |
Figure 6 - Minimum Mantel Clearances Without Using Hood
ances shown in Figure 7 when using hood.
NOTICE: Surface temperatures of adjacent walls and mantels be- come hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these tempera- tures meet the requirement of the national product standard. Fol- low all minimum clearances shown in this manual.
12"
10"
8"
6"
2 1/2"
Minimum Non-
Combustible
Material
Mantel Shelf
Underside of
Mantel Shelf
All minimum distances are in inches
8" | 12" | 15" | 18" | 20" |
Min. |
|
|
|
|
Top of Fireplace
Opening
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:
•operate the logs only with the flue damper open
•raise the mantel to an accept- able height
•remove the mantel
Hood (GA6050, | Distances to |
GA6052 or GA6053) | Underside of |
| Mantel |
Figure 7 - Minimum Mantel Clearances When Using Hood
FLOOR CLEARANCES
A.If installing appliance on the floor level, you must maintain the minimum distance of 14" to combustibles (see Figure 8).
B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combus- tible flooring (see Figure 9).
| Combustible | Hearth |
|
14" | Material | Combustible | |
Min. |
| 5” | Material |
|
|
| |
Min. |
| ||
|
| ||
Figure 8 - Minimum Fireplace Clearances | Figure 9 - Minimum Fireplace Clearances | ||
If Installed at Floor Level |
| Above Combustible Flooring | |
|
|
| Continued |