10 Electrical Information

A. Wiring Requirements

NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA 70-latest edition or the Canadian Electric

Code CSA C22.1.

This appliance comes standard with a 120 VAC cord assembly which has a female plug in to accommodate all control options and accessories. See Figure 10.5. This is required for use of optional accessories (standing pilot ignition) or proper operation of the appliance (IntelliFire Ignition). An outlet box may be installed in a bottom back corner of the existing solid fuel masonry or factory built fi replace to plug in the cord assembly, or the supplied power cord may be routed out onto the hearth to a nearby outlet.

A 120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.

Low voltage and 120 VAC voltage cannot be shared within the same wall box.

WARNING! Risk of Shock or Explosion! DO NOT wire 120V to the valve or to the appliance wall switch. Incor- rect wiring will damage controls.

Determine if the appliance uses an Intellifire ignition system or standing pilot ignition system.

Open the control access panel or remove the decorative front.

A red or black ignitor button (as shown in Figure 10.1) indicates this appliance is standing pilot ignition.

RED OR BLACK IGNITOR BUTTON

Figure 10.1 Ignitor Button

B. Standing Pilot Ignition System Wiring

The standing pilot ignition system wiring DOES NOT require a 120 VAC supply to operate.

To power appliance with 120VAC to operate a fan or remote control, an outlet box may be installed in a bottom back corner of the existing solid fuel masonry or factory built fireplace to plug in the cord assembly or the supplied power cord may be routed out onto the hearth to a nearby outlet.

NOTICE: DO NOT wire 120 VAC to the millivolt valve! This

will damage the valve.

If using a thermostat use one compatible with a millivolt gas valve system:

-Install the thermostat in the location as indicated in the thermostat instructions to ensure proper operation of appliance.

-Use low resistance thermostat wire for wiring from ignition system to the wall switch and thermostat.

-Keep wire lengths short as possible by removing any excess wire length.

C. IntelliFire Ignition System Wiring

Wire an outlet box (120VAC) in the bottom back corner of the existing solid fuel masonry or factory built fireplace to plug in the cord assembly. The supplied cord assembly may also be routed out onto the hearth to a nearby outlet.

WARNING! Risk of Shock or Explosion! DO NOT wire IPI controlled appliance junction box to a switched circuit. Incorrect wiring will override IPI safety lockout.

Refer to Figure 10.2, IPI Wiring Diagram.

This appliance is equipped with an IntelliFirecontrol valve which operates on a 3 volt system.

Plug the 3 volt AC transformer plug into the cord assembly to supply power to the unit OR install 4 AA cell batteries (not included) into the battery pack before use.

NOTICE: Batteries should not be placed in the battery pack while using the transformer. Remove batteries before using the transformer, and unplug the transformer before installing the batteries. Battery polarity must be correct or module damage will occur.

ON/OFF Switch

An ON/OFF switch is included with the appliance surround and should be attached to surround/facing. (See Installation instructions for remote control/fronts).

If desired an additional wall switch or thermostat may be added to system.

Heatilator • NDI30, NDI30-SP, NDI35, NDI35-SP, NDI30-SPFK, NDI35-SPFK2226-900 Rev. G • 4/11

25

Image 25
Contents What to do if you smell gas ModelsHOT Surfaces Homeowner Reference Information CongratulationsXxxxxxxx User Guide Table of ContentsLimited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Listing and Code Approvals Operating Instructions User Guide Gas Fireplace SafetyYour Fireplace Remote Controls, Wall Controls and Wall Switches Fixed Glass AssemblyClear Space Before Lighting FireplaceFinal inspection by Lighting Instructions IPIWhat to do if YOU Smell GAS GAS ValveLighting Instructions Standing Pilot For Your Safety Read Before Lighting Lighting InstructionsIssue Solutions Frequently Asked QuestionsAfter Appliance is Lit Maintenance Tasks-Homeowner Maintenance and ServiceGlass Cleaning Remote ControlGasket Seal and Glass Assembly Inspection Maintenance Tasks-Service TechnicianVenting LogsStanding Pilot Flame Patterns Burner Ignition and OperationTypical Appliance System Getting StartedTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Minimum Fireplace Opening Fireplace Size RequirementsTOP View Front View Side View Minimum Fireplace Size NDI35 NDI30Side View TOP View Mantel and Wall ProjectionsVent Termination Minimum Clearances Termination LocationsInstallation Preparation Connecting Vent Pipe Installing Vent Pipe and ApplianceVent Limits Venting Componentsfi replace opening Placing, Securing and Leveling the Appli- anceMasonry Installing Adaptor and Termination CapFactory Built Wood Burning Damper Flashing Kit OptionalFuel Conversion Gas InformationGas Pressure Gas ConnectionStanding Pilot Ignition System Wiring Wiring RequirementsIntelliFire Ignition System Wiring Electrical InformationRED Pilot Assembly Thermocouple ThermopileValve WHT Blower Plug 120V Existing Outlet Temperature Sensor Switch Optional Accessories RequirementsInstallation for Fan Optional Clearances to Mantels or other Combustibles above Appliance FinishingAppliance Setup Install the Log Assembly Log Set Assembly LOGS-NDI30 Models NDI30, NDI30-SPLOG #5 LOG #6LOG Log Set Installed Log Set Assembly LOGS-NDI35 Models NDI35, NDI35-SPGrate Tine Slot Air Shutter Settings Air Shutter SettingNDI30 NDI35 Symptom Possible Causes Corrective Action TroubleshootingStanding Pilot Ignition System Symptom Possible Cause Corrective Action TroubleshootingIntelliFire Ignition System Ues to spark, and main Model Dimensions Appliance Dimension DiagramReference Materials Direct Vent Flex Liner Kits Vent Kits ComponentsContact Information