Carrier 48SS Selection procedure with example, Manual Outdoor AIR Damper Filter Racks and Filters

Page 13

MANUAL OUTDOOR AIR DAMPER

FILTER RACKS AND FILTERS

ACCESSORY

PART NUMBER

``A''

FILTER

CPFILTRK001A00

2111¤16

CPFILTRK002A00

3111¤16

RACK

CPFILTRK003A00

2511¤16

 

Selection procedure (with example)

IDetermine cooling and heating requirements at design conditions:

Given:

Required Cooling Capacity (TC) . . . . . . 34,000 Btuh Sensible Heat Capacity (SHC) . . . . . . . 24,000 Btuh Required Heating Capacity . . . . . . . . . . 60,000 Btuh Condenser Entering-Air Temperature . . . . . . . . 95 F Indoor-Air Temperature . . . . . . . 80 F edb, 67 F ewb Evaporator-Air Quantity . . . . . . . . . . . . . . . 1200 cfm External Static Pressure . . . . . . . . . . . . . . . 0.2 in. wg Electrical Characteristics (V-Ph-Hz) . . . . . . . 208-1-60

II Select unit based on required cooling capacity.

Enter Cooling Capacities table at condenser entering temperature of 95 F. Unit 48SS036 at 1200 cfm and 67 F ewb (entering wet bulb) will provide a total ca- pacity of 36,000 Btuh and an SHC of 26,200 Btuh. Calculate SHC correction, if required, using Note 4 under Cooling Capacities tables.

IIISelect heating capacity of unit to provide design condition requirement.

In the Heating Capacities and Ef®ciencies table on page 5, note that unit 48SS036080 will provide 64,800 Btuh with an input of 80,000 Btuh.

IV Determine fan speed and power requirements at design conditions.

Before entering the air delivery tables, calculate the total static pressure required. From the given, the Wet Coil Pressure Drop table, and the Filter Pressure Drop table on page 18, ®nd at 1200 cfm:

External static pressure

0.20 in. wg

Wet coil

0.088 in. wg

Filter

0.13 in. wg

Total static pressure

0.42 in. wg (rounded)

 

Enter the table for Dry Coil Air Delivery Ð Horizontal Discharge for 230 and 460 V on page 16. For 208 v operation, deduct 10% from value given. The fan will deliver 1233 cfm at 0.4 external static pressure (1370 x 0.9) at high speed and 852 cfm at 0.5 external static pressure (946 x 0.9) at low speed. The fan speed should be set at high to satisfy job requirements.

VSelect unit that corresponds to power source available.

The Electrical Data table on page 24 shows that the unit is designed to operate at 208-1-60.

13

Image 13
Contents Easy installation Features/BenetsConvertible duct conguration Efcient operationDurable, dependable components Model number nomenclature Table of contentsCooling Capacities and Efficiencies ARI* capacitiesOutdoor Sound ONE-THIRD Octave Band Data Ð Decibels Seer ÐHeating Capacities and Efficiencies Unit 48SS Heating Input Output Capacity TemperatureRise Range F AfuePhysical data Field-installed accessories Options and accessoriesUnit with Optional Base Rail 48SS018-042 Without Optional Base Rail Base unit dimensions48SS018-042 with Optional Base Rail Electrical Unit Weight Corner Weight Unit HeightUnit Characteristics Electrical Unit Weight Corner Weight48SS048,060 Without Optional Base Rail 48SS048,060 with Optional Base Rail Unit Electrical Unit WeightRoof Curb Dimensions Accessory dimensionsPart Number Accessory Part Number Selection procedure with exampleManual Outdoor AIR Damper Filter Racks and Filters FilterCooling Capacities Performance dataCooling Capacities Unit Motor 460 Volt Horizontal Discharge Size DRY Coil AIR DELIVERY* Ð Horizontal DischargeSpeed Unit DRY Coil AIR DELIVERY* Ð Vertical Discharge460 Volt Vertical Discharge Size Unit Size Airflow Pressure Drop WET Coil Pressure DropUnit Size Filter Horizontal Discharge Typical piping and wiringDownflow Discharge Application data Typical control wiring schematic 48SS030-060 208/230-3-60 Tran 48SS036-060Electrical data Sequence of operation ControlsHvac Guide Specications Guide specicationsPage Carrier Corporation · Syracuse, New York