Guide speci®cations
Packaged Heating/Cooling Units
Constant Volume Application
HVAC Guide Speci®cations
Size Range: 11¤2 to 5 Tons, Nominal Cooling 40,000 to 140,000 Btuh, Nominal Input Heating
Carrier Model Number: 48SS
Part 1 Ð General
1.01SYSTEM DESCRIPTION
Outdoor rooftop mounted, gas heating/electric cool- ing unit utilizing a rotary, reciprocating, or scroll her- metic compressor for cooling duty. Unit shall discharge supply air downward or horizontally as shown on con- tract drawings. Outdoor fan/coil section shall have a
1.02 QUALITY ASSURANCE
A.Unit shall be rated in accordance with ARI Standards 210/240 and 270.
B.Unit shall be designed in accordance with UL Stand- ard 564.
C.Unit shall be UL listed and CSA certi®ed as a total package for safety requirements.
D.Roof curb shall be designed to conform to NRCA Standards.
E.Insulation and adhesive shall meet NFPA 90A re- quirements for ¯ame spread and smoke generation.
F.Cabinet insulation shall meet ASHRAE standard no. 62.
1.03DELIVERY, STORAGE, AND HANDLING
Unit shall be stored and handled per manufacturer's recommendations.
Part 2 Ð Products
2.01EQUIPMENT A. General:
B.Unit Cabinet:
1.Unit cabinet shall be constructed of phosphated,
2.Cabinet panels shall be easily removed for servicing.
3.Indoor blower compartment interior cabinet sur- faces shall be insulated with a minimum
4.Unit shall utilize a sloped condensate drain pan. External trap required.
C.Fans:
1.The indoor (evaporator) fan shall be 2- or
2.Fan wheel shall be made from steel, be double- inlet type with forward curved blades with corro- sion resistant ®nish and be dynamically balanced.
3.Outdoor (condenser) fan shall be of the direct driven, propeller type with aluminum blades riv- eted to corrosion resistant steel spiders, be dy- namically balanced, and discharge air vertically upwards and horizontally.
D.Compressor:
1.Fully hermetic compressor with
2.Rotary compressors shall be standard on unit size 018. Reciprocating compressors shall be stand- ard on unit sizes
E.Coils:
Evaporator and condenser coils shall have aluminum plate ®ns mechanically bonded to seamless copper tubes with all joints brazed. Tube sheet openings shall be belled to prevent tube wear.
F.Heating Section:
1.
2.
3.The heat exchangers shall be constructed of alu- minized steel for corrosion resistance.
4.Burners shall be of the
5.Integrated gas control board shall provide control of heating and simplify troubleshooting through its
6.All gas piping and electric power shall enter the unit cabinet at a single location.
G.Refrigerant Components:
Refrigerant components shall be of the Acutrol™ feed system type.
H.Controls:
Unit shall be complete with