Guide speci®cations

Packaged Heating/Cooling Units

Constant Volume Application

HVAC Guide Speci®cations

Size Range: 11¤2 to 5 Tons, Nominal Cooling 40,000 to 140,000 Btuh, Nominal Input Heating

Carrier Model Number: 48SS

Part 1 Ð General

1.01SYSTEM DESCRIPTION

Outdoor rooftop mounted, gas heating/electric cool- ing unit utilizing a rotary, reciprocating, or scroll her- metic compressor for cooling duty. Unit shall discharge supply air downward or horizontally as shown on con- tract drawings. Outdoor fan/coil section shall have a blow-thru design for minimum sound levels.

1.02 QUALITY ASSURANCE

A.Unit shall be rated in accordance with ARI Standards 210/240 and 270.

B.Unit shall be designed in accordance with UL Stand- ard 564.

C.Unit shall be UL listed and CSA certi®ed as a total package for safety requirements.

D.Roof curb shall be designed to conform to NRCA Standards.

E.Insulation and adhesive shall meet NFPA 90A re- quirements for ¯ame spread and smoke generation.

F.Cabinet insulation shall meet ASHRAE standard no. 62.

1.03DELIVERY, STORAGE, AND HANDLING

Unit shall be stored and handled per manufacturer's recommendations.

Part 2 Ð Products

2.01EQUIPMENT A. General:

Factory-assembled, single-piece heating and cooling unit. Contained within the enclosure shall be all fac- tory wiring, piping, controls, refrigerant charge (R-22), and special features required prior to ®eld start-up.

B.Unit Cabinet:

1.Unit cabinet shall be constructed of phosphated, zinc-coated prepainted steel, capable of withstand- ing 500 hours in salt spray.

2.Cabinet panels shall be easily removed for servicing.

3.Indoor blower compartment interior cabinet sur- faces shall be insulated with a minimum 1¤2-in. thick, ¯exible cleanable insulation, coated on the air side. Aluminum foil-faced cleanable insulation shall be used in the entire section.

4.Unit shall utilize a sloped condensate drain pan. External trap required.

C.Fans:

1.The indoor (evaporator) fan shall be 2- or 3-speed direct-drive, as shown on equipment drawings.

2.Fan wheel shall be made from steel, be double- inlet type with forward curved blades with corro- sion resistant ®nish and be dynamically balanced.

3.Outdoor (condenser) fan shall be of the direct driven, propeller type with aluminum blades riv- eted to corrosion resistant steel spiders, be dy- namically balanced, and discharge air vertically upwards and horizontally.

D.Compressor:

1.Fully hermetic compressor with factory-installed vi- bration isolation.

2.Rotary compressors shall be standard on unit size 018. Reciprocating compressors shall be stand- ard on unit sizes 024-042. Scroll compressors shall be standard on unit sizes 048 and 060.

E.Coils:

Evaporator and condenser coils shall have aluminum plate ®ns mechanically bonded to seamless copper tubes with all joints brazed. Tube sheet openings shall be belled to prevent tube wear.

F.Heating Section:

1.Induced-draft combustion type with energy saving direct spark ignition system and redundant main gas valve.

2.Induced-draft motors shall be provided with solid- state hall effects sensor to ensure adequate airflow for combustion.

3.The heat exchangers shall be constructed of alu- minized steel for corrosion resistance.

4.Burners shall be of the in-shot type constructed of aluminum coated steel.

5.Integrated gas control board shall provide control of heating and simplify troubleshooting through its built-in diagnostic function. The IGC shall pro- vide timed control of indoor-fan functioning and burner ignition. A light-emitting diode (LED) shall provide diagnostic information. The IGC board shall also contain anti-short cycle protection for gas heat operation.

6.All gas piping and electric power shall enter the unit cabinet at a single location.

G.Refrigerant Components:

Refrigerant components shall be of the Acutrol™ feed system type.

H.Controls:

Unit shall be complete with self-contained low-voltage control circuit.

26

Image 26
Contents Convertible duct conguration Features/BenetsEasy installation Efcient operationDurable, dependable components Table of contents Model number nomenclatureOutdoor Sound ONE-THIRD Octave Band Data Ð Decibels ARI* capacitiesCooling Capacities and Efficiencies Seer ÐRise Range F Unit 48SS Heating Input Output Capacity TemperatureHeating Capacities and Efficiencies AfuePhysical data Unit with Optional Base Rail Options and accessoriesField-installed accessories Base unit dimensions 48SS018-042 Without Optional Base RailUnit Electrical Unit Weight Corner Weight Unit Height48SS018-042 with Optional Base Rail 48SS048,060 Without Optional Base Rail Electrical Unit Weight Corner WeightCharacteristics Unit Electrical Unit Weight 48SS048,060 with Optional Base RailPart Number Accessory dimensionsRoof Curb Dimensions Manual Outdoor AIR Damper Filter Racks and Filters Selection procedure with exampleAccessory Part Number FilterPerformance data Cooling CapacitiesCooling Capacities Speed DRY Coil AIR DELIVERY* Ð Horizontal DischargeUnit Motor 460 Volt Horizontal Discharge Size 460 Volt Vertical Discharge Size DRY Coil AIR DELIVERY* Ð Vertical DischargeUnit Unit Size Filter WET Coil Pressure DropUnit Size Airflow Pressure Drop Downflow Discharge Typical piping and wiringHorizontal Discharge Application data Typical control wiring schematic 48SS030-060 208/230-3-60 48SS036-060 TranElectrical data Controls Sequence of operationGuide specications Hvac Guide SpecicationsPage Carrier Corporation · Syracuse, New York